READ THIS INSTRUCTION SHEET AND THE SAFETY WARNINGS
CAREFULLY BEFORE INSTALLING AND SAVE IT FOR FUTURE USE
General Features
The DA-004N024PX Series Actuators are direct-mount, non spring return electric
actuators that operate on AC 24V power supply. All models are compact in size, and are
easily installed on Variable Air Volume (VAV) boxes, Variable Air Volume and
Temperature (VVT) two-position zone applications, or small to medium-sized dampers.
The DA-004N024PX Series Electric Non-Spring Return Actuators provide a running
torque 4 Nm. Employing a synchronous motor, these actuators provide proportional
control with selectable 0-10 or 2 -10 VDC.
Figure 1: Dimensions in mm
(a). Adapter for:
Round spindles: Ø up to 13 mm Square splindles:
Installation and adjustment
Mounting Instructions
Figure 2: Mounting the Actuator onto the Damper Shaft
(a). Damper
(b). Damper Shaft
Figure 3: Positioning the Actuator
(a). Mounting surface
(b). Gear Release Button
(c). Approximately a 5 mm Gap
Figure 4: Inserting the Screw into the Shoulder Washer
(a). Gear Release Button
(b). Self-Drilling Sheet Metal Screw
(c). Cover Screw
(d). Shoulder Washer
(e). Plastic Washer Retainer
• Grasp the damper shaft firmly with pliers and rotate the damper fully closed.
• Press and hold the gear release lever, and rotate the actuator coupler to the fully
closed position.
• Make a note of the rotation range and direction, either Clockwise (CW)
or Counterclockwise (CCW), required to close the damper.
• Position the actuator onto the damper shaft so that the damper shaft protrudes
throught the actuator coupler, as illustrated in Figure 2.
Ordering Codes
Codes
Descriptions
DA-004N024PX
4 Nm, AC 24 V with 1.2 PVC cable
Technical Specifications
Product Codes
Power Requirements
Control Type
Input Signal
Feedback Signal
Motor Input Impedance
Running Torque
Travel Time (for 90° of Rotation)
Rotation Range
Cycles
Audible Noise Rating
Electrical Connections
Mechanical Connections
Enclosure
Ambient Conditions
- Operating -20 to 60 °C; 90% RH Maximum, Noncondensing
- Storage -40 to 85 °C; 90% RH Maximum, Noncondensing
Shipping Weight
Compliance
1
IS_DA-004N024PX_14-88360-03273_Rev. -_09 2017
up to 10 mm
DA-004N024PX
AC 24 V +25% / -20% at 50/60 Hz / 3.6 VA
Modulating
DC 0(2) to 10 V or 0(4) to 20 mA with field furnished, 500 ohm resistor
DC 0(2)...10 V - Corresponds to input span selection (DC 10V at 1 mA)
200 ohms Nominal
4 Nm
60 Seconds at 60 Hz / 72 Seconds at 50 Hz
93° ±3°, CW or CCW
100,000 Full Stroke Cycles; 2,500,000 Repositions at Rated Running Torque
35 dBA Nominal at 1 m
1.2 m Polyvinyl Chloride (PVC) cable with 0.75 mm
Up to13 mm Diameter Round Damper Shafts, or 10 mm Square Damper Shafts
IP 42
0.5 Kg
Distech Controls SAS declares that these products are in compliance with the essential requirements and other relevant provisions of the EMC
Directive and Low Voltage Directive
• Be certain that the actuator is in the desired mounting position parallel to the mounting
surface, as illustrated in Figure 3.
• Hold the acuator in place on the damper shaft, and insert the self-drilling sheet metal
screw through the shoulder washer as illustrated in Figure 4.
• Place a 8 mm socket on the screw and use a drill and extensions to drill the screw
into the mounting surface.
• Drive the screw until it is tight against the washer.
IMPORTANT: Do not overtighten the mounting screw. Overtightening may strip
the threads.
• Tighten the square coupler bolt to the shaft using an 8 mm wrench or 10 mm 12-point
socket. Tighten to 11 to 15 Nm.
Selecting the direction of rotation
Figure 5: DA-004N024PX Factory Switch Setting
DA-004N024PX actuators are factory set for Direct Acting (DA) mode and for a DC 0 to
10 V input control signal. To change the factory settings (DA, 0-10 V), remove the
actuator cover and adjust the switches on the circuit board as shown in Figure 5.
Wiring
WARNING: Risk of Electric Shock. Disconnect the power supply before
making electrical connections to avoid electric shock.
WARNING: Risk of Property Damage. Do not apply power to the system
before checking all wiring connections. Short circuited or improperly
connected wires may result in permanent damage to the equipment.
Wiring Diagrams
Figure 6: DA-004N024PX Control Wiring Diagram
WARNING: The electrical connections for the actuators must be
executed in accordance with the relevant legal requirements.
In order to avoid any personal injury or damage to the equipment
or other property, always isolate the power supply before commencing
any work on electrical wiring. In order to avoid danger to property,
it is important for the equipment to be used solely for which
it is intended.
WARNING: The integrated circuits in actuator are sensitive to static
electricity. Take suitable precaution.
2
conductors and 6 mm ferrule ends
This document is subject to change without notice