Input Wiring

Before connecting a sensor to the controller, refer to the installation guide of the equipment manufacturer.
£
For a wire length less than 75' (23m), either a shielded or unshielded 18AWG wire may be used.
£
For a wire up to 200' (61m) long, a shielded 18AWG wire is recommended.
£
The shield of the wire should be grounded on the controller side only and shield length should be kept as short as possible.
Input can be connected as follows. Table 1 shows the input designation for the ECx-400 UUKL I/O Extension Module.
Sensor Input Type
£
Dry Contact input.
£
Pulsed input
£
RTD input (for example, 1000Ω).
£
Thermistor Input (for example, 10kΩ type II and III).
£
Resistive input, (for example, use with 10kΩ and 100kΩ potentiome-
ters).
£
0 to 20mA input used with a 2-wire, 0 to 20mA sensor powered by the
ECx-400 UUKL internal 15VDC power supply.
£
0 to 20mA input used with a 2-wire, 0 to 20mA sensor powered by an
external 24VDC power supply.
£
0 to 20mA input used with a 3-wire, 0 to 20mA sensor powered by an
external 24VAC power supply.
£
0 to 20mA input used with a sensor powered by its own power source.
£
Voltage input used with a 3-wire 0 to 10VDC or 0 to 5VDC sensor
powered by an external 24VAC power supply
£
Voltage input used with a 0 to 10VDC or 0 to 5VDC sensor powered
by its own power source.
6 / 16
Input Des-
Input Connection Diagram
ignation
UIx
Digital Dry Contact
UIx
Thermistor
UIx
UIx
+
Sensor
-
UIx
Sensor
UIx
Sensor
UIx
Sensor
UIx
0-10V
Sensor
UIx
0-10V
Sensor
UIx
NO-NC
COM
UIx
RTD/
COM
Potentiometer
UIx
10kΩ
COM
Jumper
Setting
0-10V
+15VDC
0-20mA
249Ω
UIx
0-20mA
COM
Jumper
Setting
0-10V
0-20mA
249Ω
UIx
0-20mA
-
+
COM
24VDC
Jumper
Setting
0-10V
0-20mA
UIx
249Ω
0-20mA
+
Common
COM
24VAC
AC
Jumper
Setting
0-10V
0-20mA
UIx
249Ω
0-20mA
+
-
COM
UIx
+
Common
COM
24VAC
AC
UIx
+
-
COM
To Digital
Input
To Analog-
To-Digital
Converter
To Analog-
To-Digital
Converter
To Analog-
To-Digital
Converter
Controller
0-20mA Input
Equivalent
Circuit
To Analog-
To-Digital
Converter
Controller
0-20mA Input
Equivalent
Circuit
To Analog-
To-Digital
Converter
Controller
0-20mA Input
Equivalent
Circuit
To Analog-
To-Digital
Converter
Controller
0-20mA Input
Equivalent
Circuit
To Analog-
To-Digital
Converter
To Analog-
To-Digital
Converter