Distech Controls Allure EC-Smart-Comfort-SF-Dl Installatiehandleiding - Pagina 9
Blader online of download pdf Installatiehandleiding voor {categorie_naam} Distech Controls Allure EC-Smart-Comfort-SF-Dl. Distech Controls Allure EC-Smart-Comfort-SF-Dl 13 pagina's.
The indicated addressing ranges are specific to each group of devices.
4 different Subnet ID codifications are used on the ECx Subnetwork :
£
1 for Allure EC-Smart-Vue Series sensors
£
1 for Allure EC-Smart-Comfort and Allure EC-Smart-Air sensors
£
1 for EC-Multi-Sensors
£
1 for ECx-Light/Blind Series expansion modules
Consequently, an Allure EC-Smart-Vue sensor and an Allure EC-Smart-Air sensor may share the same Subnet ID, but an Allure EC-
Smart-Air sensor and an Allure EC-Smart-Comfort sensor must have a different Subnet ID.
About the Subnetwork Bus
The controllers use the subnetwork bus to communicate with the room devices (see each controller's datasheet for compatibility), with a standard Cat 5e
cable. Devices are connected in a daisy-chained fashion to the controller's Subnet Port. To ensure proper operation, it is recommended to distribute the
sensors as evenly as possible throughout the length of the subnetwork.
The maximum length of the Communicating Sensor subnetwork bus is 600 ft (180 m).
Figure 9:
Subnetwork Bus Overview
For ECB/ECL-PTU Series controllers, the maximum length between two consecutive devices on the sub-network bus is 100 ft (30 m).
9 / 13