7.
Output: Use the <ROLL> key to toggle the output OFF (normal
operation), MIN (minimum output) or MAX (maximum output) for
testing purposes. Press either <SAVE> or <MENU> to set it back
to OFF and advance to the next item.
8.
Calibrat:
This item is used for 0 ppm gas calibration and is
explained in the
Calibration
9.
Calibrat: This item is used for 1000 ppm gas calibration and is
explained in the
Calibration
10. Calibrat: This item is used for 20,000 ppm gas calibration and is
explained in the
Calibration
Item 12 is only available if the cover is equipped with a viewable LCD,
otherwise the menu skips directly to step 13.
11. BackLite: Use the <ROLL> key to enable or disable the LCD
backlight. When enabled the backlight is always on, when
disabled it never lights. Press the <SAVE> key to save the
setting. The factory default is Enable.
12. Restore: Press the <SAVE> key to restore calibration to original
factory settings.
13. Menu: Press <SAVE> to exit the menu and return to normal
operation or <MENU> to repeat the menu.
4/5
section.
section.
section.
Product Components
Figure 5. Product Components