Quick Start Guide
COOLMAX SR
1)
Remove the access cover at the bottom of the COOLMAX SR
unit by removing the two M3 screws on the bottom of the
enclosure as shown in image.
2)
All COOLMAX SR wiring must enter the unit via a conduit fitting
that needs to be inserted by user prior to inserting any cabling.
The conduit will be located inside the unit at delivery.
3)
Remove the conduit from inside the unit and fix to the bottom
of the COOLMAX SR Unit by attaching the conduit on the
outside and the locking nut on the inside as shown in image
WARNING: The chassis of the COOLMAX SR should be earthed by installing
an earthed ring terminal under the bottom left mounting bolt of the chassis. DO
NOT EARTH THE ARRAY in any way if a negative earth is used for the batteries
or DC system.
SRHVW
IMPORTANT: AERL recommends the use of
6kA, 8kA or 10kA DC rated circuit breakers
with an appropriate voltage rating on both
input and output.
4)
Double or triple ganged circuit-breakers
can be connected in series to give the
desired voltage rating as shown in the
picture above. It is important that the peak
voltages are taken into account when
SRMVW
selecting
5)
AERL recommends that the COOLMAX SR
be utilized in a floating system whenever
possible.
recommended that a lightning conductor be
provided nearby to prevent damage to PV
equipment, batteries and the COOLMAX SR.