Operating Instructions
Transducer for phase angle or power factor SINEAX G 536
Safety precautions to be strictly observed are marked
with following symbols in the Operating Instructions:
Contents
1. Read first and then ... ............................................... 11
2. Brief description ....................................................... 11
3. Technical data .......................................................... 11
4. Mounting ................................................................... 12
5. Electrical connections ............................................... 12
6. Commissioning and maintenance ............................ 13
7. Releasing the transducer .......................................... 13
8. Dimensional drawing ................................................ 14
9. Application notes ...................................................... 14
10. Instruments admissions ............................................ 14

1. Read first and then ...

The proper and safe operation of the device
assumes that the Operating Instructions is
read carefully and the safety warnings given
in the various Sections
4. Mounting
5. Electrical connections
are observed.
The device should only be handled by appropriately
trained personnel who are familiar with it and authorised
to work in electrical installations.

2. Brief description

The transducer SINEAX G 536 measures the phase angle or
power factor between current and voltage of a single or
3 phase balanced network having a sine wave form.
The output signal, in the form of a load independent DC
current or voltage, is proportional to the phase angle ϕ resp.
power factor cosϕ between the 2 measured quantities current
and voltage.

3. Technical data

Measuring input
Measured quantity:
Phase angle or power factor
Within - 180 - 0 - + 180 °el or
Measuring range:
-1-ind-0-cap-1-ind-0-cap- -1
but clear indication only to
-175-0- +175 °el
measuring span ≥ 20 °el
≥ 10 to 400 Hz (min. 40 Hz with
Nominal frequency:
power supply from measuring input)
Nominal input
≥ 10 to 690 V (min. 24 V, max. 230 V,
voltage:
acc. to build-in power pack, with
power supply from measuring input)
Nominal input current: ≥ 0.5 to 6.0 A
Measuring output
DC current:
0 - 1 to 0 - 20 mA
1 - 5 to 4 - 20 mA
± 1 to ± 20 mA
Burden voltage:
- 12 V / 15 V
max. [kΩ] ≤
External resistance:
R
ext
resp. ≤
I
= Full output value
AN
DC voltage:
0 - 1 to 0 - 10 V
0.2 - 1 to 2 - 10 V
± 1 to ± 10 V
Load capacity:
Max. 4 mA
Power supply
AC/DC power pack (DC or 40 - 400 Hz)
Rated voltage
85 - 230 V DC / AC
24 - 60 V DC / AC
≤ 2.5 W resp. ≤ 3.5 VA
Power consumption:
Options
Connected to the low
tension terminal side:
24 V AC or 24 - 60 V DC, see Fig. 4
Power supply from
measuring input
≥ 24 - 60 V AC or 85 - 230 V AC,
(self powered):
see Fig. 3
Please note the max. and min. measuring input voltage!
Type label
Input voltage
inscription
range
= internal power
supply range
Self powered
by 1/2
24 - 60 V AC
(int. 24-60 V)
Self powered
by 1/2
85 - 230 V AC
(int. 85-230 V)
15 V
I
[mA]
AN
- 12 V
- I
[mA]
AN
Tolerance
DC - 15 to + 33%
AC ± 15%
Tolerance Power
supply
connec-
tion
Internal
± 15%
measuring
input
11