In normal operation, the lowest output value is 30.5mV, which is 405 ppm equivalent CO2.
The increase in output voltage is in the ratio of 1mV per 11.6ppm CO2.
As an example, an output voltage of 60.2mV corresponds to 698.3ppm CO2.
8
Data output 1-Wire Controller / 1-Wire Gateway
For the 1-Wire Multisensor Pro II, the following measured values are output via the 1-Wire controller/1-Wire
gateway.
Data output:
1_EVT|12:27:40
1_OWD1_1|2008
1_OWD1_2|511
1_OWD1_3|850
1_OWD1_4|1200
1_OWD1_5|80000
Further information on the options and commands can be found in the current 1-Wire Controller/
1-Wire Gateway documentation.
9
Integration in IP-Symcon / ESERA-Station
Via our website we provide ESERA IP-Symcon software modules for reading the
1-Wire Multisensor into IP-Symcon via 1-Wire Controller/1-Wire Gateway. So no scripts are necessary.
Details can be found on the ESERA website at „Kompatible Steuerungen/Zentralen/IP-Symcon-Integration"
https://www.esera.de/kompatible-steuerungen-zentralen/ip-symcon-integration/
For the conventional connection via 1-Wire Bus Coupler the sensor values have to be calculated according
to the given formulas.
10
Integration in Loxone
Via the shop we provide a sample project for reading in the 1-Wire Multisensor via 1-Wire controller 1/1-Wire
gateway, among other things. For details see here:
https://www.esera.de/kompatible-steuerungen-zentralen/loxone-integration/demo-1-wire-controller-1-loxone-
integration/
11
Integration in FHEM
For the integration into the open source automation software FHEM we provide a software module for
reading the 1-Wire Multisensor via 1-Wire controller/1-Wire gateway. This means that evaluation scripts are
no longer necessary.
Details can be found on the ESERA website at „Kompatible Steuerungen - Zentralen / FHEM-Integration"
https://www.esera.de/kompatible-steuerungen-zentralen/fhem-integration/
12
Commissioning and Warm-up
The Air Quality Sensor integrated in the 1-Wire Multisensor requires a short warm-up time of approx. 7
minutes. During this time, 0% air quality is constantly output via the 1-Wire interface. After the warm-up time,
the Air Quality Sensor automatically switches to normal operation.
13
Calibration / Adjustment
The 1-Wire Multisensor Pro II is pre-calibrated. Calibration is not necessary and is possible.
14
Measuring accuracy
The sensor elements within the 1-Wire Multisensor Pro II are pre-calibrated. Please note that the measuring
accuracy may possibly be reduced towards the measuring range limits and at very high and low operating
temperatures.
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH 2021
www.esera.de
=> Controller No._module No._Data set|temperature (°C) example: 20,08 °C
=> Controller No._module No._Data set|voltage VCC (V)
=> Controller No._module No._Data set|humidity (rF) example: 85,0%
=> Controller No._module No._Data set|dew point (°C) example: 12,00 °C
=> Controller No._module No._Data set| air quality(ppm CO2) ex.: 800,00 ppm