6. Technical data
Measuring input
DC current:
Limit values
0...0.1 to 0...40 mA
also live-zero,
start value > 0 to ≤ 50% final va-
lue
or span 0.1 to 40 mA
between – 40 and 40 mA
also bipolar asymmetrical
R
DC voltage:
Limit values
0...0.06 to 0...40,
also live-zero,
start value > 0 to ≤ 50% final va-
lue
or span 0.06 to 40 V
between – 40 and 40 V
also bipolar asymmetrical
R
Overload:
DC current
continuously 2-fold
DC voltage
continuously 2-fold
Measuring output
DC current:
Standard ranges
0...20 mA, 4...20 mA, ± 20 mA
Limit values
0...1 to 0...20 mA
0.2...1 to 4...20 mA
– 1...0...+ 1 bis –20...0...+ 20 mA
16
(2)
Span
Channel 2
Zero
Span
Channel 1
Zero
without
function
ON
= 15 Ω
i
= 100 kΩ
i
Burden voltage:
12 V
External resistance:
R
I
AN
DC voltage:
Standard ranges
0...10 V, 2...10 V, ± 10 V
Limit values
0...1 to 0...10 V
0.2...1 to 2...10 V
– 1...0...+ 1 to – 10...0...+ 10 V
Burden:
R
U
value
Current limiter at
Approx. 1.1 ×I
R
max.:
ext
Voltage limiter
= ∞:
at R
Approx. 13 V
ext
Residual ripple in
output current:
< 0.5% p.p.
Response time:
< 50 ms
Power supply H
AC/DC power pack (DC and 45...400 Hz)
Table 1: Nominal voltages and tolerances
Nominal voltage
U
N
24... 60 V DC / AC
85...230 V
DC / AC
1
For power supply > 125 V, the auxiliary circuit should include an
1
external fuse.
≤ 1.2 W resp. ≤ 3 VA
Power input:
Accuracy data (acc. to DIN/IEC 770)
Limit error ≤ ± 0.2%
Basic accuracy:
Including linearity and reproduci-
bility errors
Environmental conditions
Commissioning
temperature:
– 10 to + 40 °C
Operating
temperature:
– 25 to + 40 °C
Storage temperature:
– 40 to + 70 °C
Annual mean
relative humidity:
≤ 75%
Altitude:
2000 m max.
Indoor use statement!
12 V
max. [kΩ] =
ext
I
[mA]
AN
= Output circuit full-scale value
U
[V]
min. [kΩ] ≥
AN
ext
5 mA
= Output circuit full-scale
AN
for current output
AN
Tolerance
DC – 15...+ 33%
AC ± 15%