esera automation 11208 Gebruikershandleiding - Pagina 2
Blader online of download pdf Gebruikershandleiding voor {categorie_naam} esera automation 11208. esera automation 11208 7 pagina's. Analog output 0-10vdc for 1-wire bus system
4
Technical data
Number of channels:
Output voltage:
Output current:
rise time (0-10V):
cut-off frequency:
output resistance:
Resolution:
Smallest resolution:
Accuracy:
Isolation:
1-Wire device:
Interface:
Operating voltage:
Current consumption:
Display:
Connection:
Note:
A 12V supply voltage is required to operate the module. The use of one of our 1-Wire Hub devices is
recommended. Avoid to connect the 12V power supply to the "data" terminal. This can cause
permanent damage to the device.
5
Ambient Conditions
Protection type:
Protection class:
Temperature, operation: 0°C bis +50°C
Air humidity:
Dimensions:
6
Conformity
EN 50090-2-2
EN 61000-4-2, ESD
EN 61000-4-3, HF
EN 61000-4-4, Burst
EN 61000-4-5, Surge
EN 61000-6-1, Fault-free operation
EN 61000-6-3, Stray radiations
RoHS
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de
1
0-10 VDC
max. 20 mA
max. 5 ms
20 Hz
ca. 100 Ohm
8 Bit
40 mV
>1% of the nominal value
min. 500VAC among 1-Wire Bus and Analog Output
DS2408 (8-fold digital I/O)
1-Wire bus (12V, data (5V signal level) and GND/Ground)
12V= (+/-10%), current consumption max. 30mA
max. 20 mA (output with 10k load)
2 x LED green, data update and supply voltage
screw-terminals (up to 2,5qmm cable cross-section)
IP20
III
10 - 92% (non-condensing)
35 x 90 x 70mm (WxHxD)
11208 V2.0 R1.0 Manual