4.2 DEHUMIDIFYING ACTION WITHOUT DEHUMIDIFIER RELAY, OA1 DIFFERENT FROM DEH
In this case the dehumidifying action is performed by setting the following parameters in this way:
tHu = c-H kind of dehumidifying by means of heating and compressor relays
oA1 different from dEH:
The heating and compressor outputs are activated together when humidity is higher than SET %RH+dbH value. Outputs are disabled when humidity
comes back to the SET %RH value.
4.2.1 Relation between cooling, heating and dehumidifying
1.
If is simultaneously present a request of cooling (temp>SET TEMP+dbt) and dehumidifying (RH > SET %RH+dbH): the cooling action has the
priority over the dehumidifying action: only the compressor relay is energised till the SET TEMP is reached at this point also the heating relay
is enabled.
2.
If is simultaneously present a request of heating (temp< SET TEMP-dbt) and dehumidifying (RH > SET %RH+dbH): the dehumidifying action
has the priority over the heating action: both the compressor and the heating relays are energised till the humidity set is reached at this point
only the heating relay is enabled.
4.3 DEHUMIDIFYING ACTION WITH DEHUMIDIFIER RELAY, OA1 = DEH
The configurable relay is used, setting the parameter oA1 =dEH.
NOTE: the LIGHT button is not more available; Two kinds of de-humidifying are available:
4.3.1 Dehumidifying action with ONLY de-humidifier relay
By setting the parameter tHu = db the de-humidifying action is performed by enabling the de-humidifier relay when the humidity is higher than SET
%RH + dbH.
The relay is switch off when humidity comes back to the SET %RH value.
4.3.2 Dehumidifying action with de-humidifier and compressor relays
By setting the parameter tHu = cHu the de-humidifying action is performed by enabling the de-humidifier and compressor relays together. when the
humidity is higher than SET %RH + dbH. The relays are switched off when humidity comes back to the SET %RH value.
If is simultaneously present a request of cooling (temp>SET TEMP+dbt) and dehumidifying (RH > SET %RH+dbH): the cooling action has the priority
over the dehumidifying action: only the compressor relay is energised till the SET TEMP is reached at this point also the de-humidifier is enabled.
5.
FA NS
The fan control mode is selected by means of the "FnC" parameter:
FnC=C-n fans will switch ON and OFF with the compressor and not run during defrost:;
FnC= O-n fans will run continuously, but not during defrost
FnC=C-y fans will switch ON and OFF with the compressor and run during defrost;
FnC=O-y fans will run continuously also during defrost
6. EXTRACTOR FAN
6.1 EXTRACTOR FAN CYCLES
The second relay is configured as extractor fan, oA2= ESt, then it is possible to make extraction cycles, both manually and automatically.
Extraction cycle can be activated both manually by pushing the UP key for 3s, and automatically by the internal time rFi. Cycle duration is set by the
rFd parameter. The cycle can be stopped also by key.
If rFI = 0 only manual cycle can be activated.
If rFd = 0 the cycle is stopped only by pushing the key.
7. MATURING CYCLE WITH DRIPPING, RUNNING AND STOPPING PHASE.
Dripping
1592017410 XLH360 GB r1.0 15.04.2005.doc
Operating Instructions
Running
Stopping
Running
Stopping
XLH360