1. Prior to installation, clean any dirt or foreign matter from connection
surfaces.
2. Install air relief valve in positions ranging from vertical (0°) to
horizontal (90°). The opening pressure will be reduced if the valve is
not mounted vertically. Do not install valve in inverted position.
3. Install air relief valve with exhaust area positioned so exhaust
vents safely (preferably down). Downward venting" prevents dirt or
debris from entering the valve during travel.
4. Threaded versions only, removable thread locking compound is
recommended for mounting.
5. Threaded versions only, thread the valve into place by hand and
tighten using a crescent wrench (or equivalent) across the hex flats.
6. Victaulic grooved, and Cam & Groove connection models come
with a lug for attaching a security chain.
Dixon Bayco air relief valves are tested at the factory and are in
proper working condition when shipped. Air relief valves are
designed to be tough and to provide long service with reasonable
care and handling.
Operation and Maintenance Instructions
Weekly visual inspection of the valve is recommended.
1. Ensure that the valve body and exhaust vents are kept clear of
buildup.
2. Ensure that exhaust vents remain clear of all obstructions.
3. Inspect the valve regularly to ensure connection tightness.
Excessive blower vibration may cause valve to loosen over time.
4. The Dixon Bayco air relief valve is assembled with tamper resistant
screws and is pre-set at the factory to customer requirements. Any
attempt to disassemble or adjust settings for any reason will void the
manufacturer's warranty.
For complete warranty information, please refer to the latest
2182 ARV
2182 Air Relief Valves
Installation
Care and Handling
Dixon Bayco Warranty
Dixon catalog.