EDI NEMA TS-1 Bedieningshandleiding - Pagina 15
Blader online of download pdf Bedieningshandleiding voor {categorie_naam} EDI NEMA TS-1. EDI NEMA TS-1 16 pagina's. Enhanced signal monitor
Red Fail
Controller Voltage Monitor, +24V Monitors
Dual Indication
Clearance Fail
Short Yellow
AC+ Interruption (disable) ......................... greater than 475 milliseconds +/- 25 milliseconds
Minimum Flash after disable .................................................... 4 to 15 seconds +/- 1 second
Start Delay Relay timer .................................................................. 2.5 seconds +/- 1 second
5.3 MECHANICAL
Height .................................................................................................................. 6.5 inches
Width ................................................................................................................... 3.0 inches
Depth (including MS connector) ........................................................................... 7.6 inches
5.4 ENVIRONMENTAL
Storage Temperature Range ........................................................................... 55 to +90 oC
Operating Temperature Range ........................................................................ 37 to +74 oC
Humidity Range ......................................................................................... 0 to 95% Relative
Eberle Design Inc.
NSM-3E Signal Monitor Unit
Operations Manual
No Fault ....................................... less than 700 milliseconds
Fault ....................................... greater than 1000 milliseconds
Typical ........................................................ 850 milliseconds
No Fault ....................................... less than 125 milliseconds
Fault ......................................... greater than 175 milliseconds
Typical ........................................................ 150 milliseconds
No Fault ....................................... less than 200 milliseconds
Fault ......................................... greater than 500 milliseconds
Typical ........................................................ 400 milliseconds
Fault .................................................... less than 2.6 seconds
No Fault .......................................... greater than 2.8 seconds
Typical ............................................................... 2.7 seconds
Page 11