Altronix AL1012ULM Installatiehandleiding - Pagina 4
Blader online of download pdf Installatiehandleiding voor {categorie_naam} Altronix AL1012ULM. Altronix AL1012ULM 17 pagina's. Multi-output access control power supply/chargers
Ook voor Altronix AL1012ULM: Installatiehandleiding (17 pagina's), Installatiehandleiding (17 pagina's)
![Altronix AL1012ULM Installatiehandleiding](/uploads/products/server2/847322/847322.jpg)
11.Connect supervisory trouble reporting devices to outputs marked [AC FAIL, LOW BAT] and [Power Fail]
supervisory relay outputs marked [NO, C, NC] on power supply board (Fig. 1A, pg. 5; Fig. 2A, pg. 6; Fig. 3A, pg. 7;
Fig. 4A, pg. 8). Use 22 AWG to 18 AWG for AC Fail & Low Battery reporting.
Note: When used in fire alarm, burglar alarm or access control applications, "AC Fail" relay must be used to provide
a visual indication of AC power on.
12. Please insure that the cover is secured with the provided Key Lock.
AL300ULM
Output
12VDC / 40 AH Battery
24VDC / 12 AH Battery
24VDC / 40 AH Battery
AL400ULM
Output
12VDC / 40 AH Battery
24VDC / 12 AH Battery
24VDC / 40 AH Battery
AL600ULM
Output
12VDC / 40 AH Battery
24VDC / 12 AH Battery
24VDC / 40 AH Battery
AL1012ULM
Output
12VDC / 12 AH Battery
AL1024ULM
Output
24VDC / 12 AH Battery
24VDC / 65 AH Battery
- 4 -
Output Voltage and Stand-by Specification Charts:
Switch
4 hr. of Stand-by &
Position
5 Minutes of Alarm
Stand-by = 2.5 amp
Closed
Alarm = 2.5 amp
Open
Stand-by = 2.5 amp
Open
Alarm = 2.5 amp
Switch
4 hr. of Stand-by &
Position
5 Minutes of Alarm
Stand-by = 4.0 amp
Closed
Alarm = 4.0 amp
Open
Stand-by = 3.0 amp
Open
Alarm = 3.0 amp
Switch
4 hr. of Stand-by &
Position
5 Minutes of Alarm
Stand-by = 6.0 amp
Closed
Alarm = 6.0 amp
Open
Stand-by = 6.0 amp
Open
Alarm = 6.0 amp
15 mins. Stand-by /
5 mins. Alarm
7.7 amp / 9.7 amp
-------------------------
24 hr. of Stand-by &
5 Minutes of Alarm
Stand-by = 1.0 amp
Alarm = 2.5 amp
Stand-by = 200mA
Alarm = 2.5 amp
Stand-by = 1.0 amp
Alarm = 2.5 amp
24 hr. of Stand-by &
5 Minutes of Alarm
Stand-by = 1.0 amp
Alarm = 4.0 amp
Stand-by = 200mA
Alarm = 3.0 amp
Stand-by = 1.0 amp
Alarm = 3.0 amp
24 hr. of Stand-by &
5 Minutes of Alarm
Stand-by = 1.0 amp
Alarm = 6.0 amp
Stand-by = 200mA
Alarm = 6.0 amp
Stand-by = 1.0 amp
Alarm = 6.0 amp
15 Minutes of Stand-by @ 10 amp
4 hr. Stand-by /
5 mins. Alarm
1.2 amp / 9.7 amp
7.7 amp / 9.7 amp
60 hr. of Stand-by &
5 Minutes of Alarm
Stand-by = 300mA
Alarm = 2.5 amp
Stand-by = 300mA
Alarm = 2.5 amp
60 hr. of Stand-by &
5 Minutes of Alarm
Stand-by = 300mA
Alarm = 4.0 amp
Stand-by = 300mA
Alarm = 3.0 amp
60 hr. of Stand-by &
5 Minutes of Alarm
Stand-by = 300mA
Alarm = 6.0 amp
Stand-by = 300mA
Alarm = 6.0 amp
24 hr. Stand-by /
5 mins. Alarm
-------------------------
1.2 amp / 9.7 amp
60 hr. Stand-by /
5 mins. Alarm
-------------------------
200mA / 9.7 amp
Mseries