OWNER'S MANUAL
0
Press NEXT
to advance
NEXT
Press NEXT
to advance
NEXT
Press the PROGRAM button to exit Advanced Setup.
About Advanced Features & Operation
CYCLES PER HOUR - The Cycles Per Hour setting
(page 16) monitors the number of times per hour
your HVAC unit may energize. For example, at a
setting of 6 cycles per hour the HVAC unit will only
be allowed to energize once every 10 minutes. The
Cycles Per Hour limit may be temporarily overridden
by pressing the WARMER or COOLER button.
TWO STAGE OPERATION - The 2nd stage of heat
(auxiliary heat) is turned on when the room temp-
erature is equal to or less than: the setpoint minus
the 1st stage deadband (one degree, adjustable),
minus the 2nd stage deadband (two degrees, non-
adjustable).
Deadband
db 2
(non-adj. 2 )
2nd Stage
1st Stage
turn on
S1-THEU21P7S
Indicates that the ther-
mostat jumper is set for
an O reversing valve
(energize in cooling) or
a b reversing valve
(energize in heating).
ON indicates that the
thermostat jumper is
set for Electric Heat
operation, or OFF for
Gas/Electric or Heat
Pump operation.
Cooling
Heating
Deadband
Deadband
db 1
db 1
(adj. 1-6 )
(adj. 1-6 )
Heat or Cool
turn on
Setpoint
Page 16
1st Stage
turn on