CVS Controls YT-1000L Producthandleiding - Pagina 2
Blader online of download pdf Producthandleiding voor {categorie_naam} CVS Controls YT-1000L. CVS Controls YT-1000L 13 pagina's. 1000l electro-pneumatic linear positioner

CVS Controls Ltd.
Product Manual: CVS Rack & Pinion Actuator
Operation Logic
As the input signal is increased, the flapper (2) get pushed by the force of the torque-motor (1). As the
gap between the flapper (2) and the nozzle (3) increases, air pressure bleeds from the pilot valve (4)
and the spool (5). As a result, the spool (5) rises and simultaneously opens the seat (7). This allows air
pressure to discharge through port OUT1 to the actuator (10). As the actuators inner pressure increases,
the actuator stem (12) will move, pushing on the feedback lever (13). This movement is transferred to
the cam (14) and pulls on the feedback spring (16). At the point of balanced force exerted by the input
signal and the feedback spring, the gap between the flapper (2) and the nozzle (3) will decrease,
stopping the movement to the actuator.
CVS Controls Ltd.
Process Management
And Instrumentation
2