AKO AKO-14545-C Beknopte handleiding
Blader online of download pdf Beknopte handleiding voor {categorie_naam} AKO AKO-14545-C. AKO AKO-14545-C 2 pagina's.
Ook voor AKO AKO-14545-C: Handmatig (2 pagina's)
1454H522 Ed.02
Quick guide
AKO-14545
AKO-14545-C
3- Quick start
By using keys N and Q, select the most suitable option according to the installation type in accordance with
PRES
1
TEMP
the table in the "WIZARD" appendix and press SET. The wizard configures the equipment parameters
and assigns the input and output functions according to the installation type chosen.
Select the refrigerant gas type used from amongst the following options:
PRES
2
TEMP
0=R134a
1=R404a
7=R407a
8=R407f
PRES
Select the primary and secondary display units from amongst the following options:
3
TEMP
0=bar-ºC; 1=psi-ºF;
Configure the rest of the parameters to their default value? :
PRES
0=No, the configuration is kept for all the parameters except for C01, C02, C04, C05 C06, C08 and C09.
4
TEMP
1=Yes, all the parameters are configured to their default value (see parameters table)
(This option does not affect parameters C01, C02, C04, C05 C06, C08 and C09)
4- "WIZARD" table
The "WIZARD" table in the appendix is divided into 3 groups of
columns. The first describes the different installation types
(number of compressors and fans, if they have an inverter, etc.)
associated with the INI option.
The second group specifies the function assigned to each relay
depending on the INI option selected.
The third group specifies the function assigned to each digital
input depending on the INI option selected.
Installation type
Stages by compressor
Compressors without
inverter
2
INI
1
1
1
1
-
2
1
2
-
3
1
3
-
4
1
4
-
Fans with inverter
5- Operation
ESC key
In the programming menu, exit the parameter without saving
changes, return to previous level or exit programming.
SET key
By pressing this key for 1 second the probe display units
change (according to parameter C09).
Pressing it for 10 seconds accesses the programming menu.
In the programming menu, it accesses the level shown on the
display or, during the setting of a parameter accepts the new
value.
N UP key
By pressing this key for 1 second probe 2 is displayed for 5
seconds (or probe 1, according to parameter P02). By pressing
a second time the probe ambient temperature value will be
shown (only if I07 or I08=3).
In the programming menu it allows scrolling around the
different levels, or during the setting of a parameter, changing
its value.
Q DOWN key
Pressing this key returns the equipment to its normal
operation after an alarm which require a reset (the causes
which triggered the alarm must have disappeared).
1- Warnings
GB
-If the equipment is used without adhering to the manufacturer's
instructions the device safety requirements could be compromised.
-The installation location of the equipment must be protected from
vibrations, water and corrosive gases where the ambient temper-
ature does not exceed the value featured in the technical data.
-To ensure a correct reading the probe must be located away from
external effects.
-The power circuit should be equipped with a switch for its
disconnection of at least 2 A, 230 V, situated near the appliance.
The cables will be fed in from the rear and will be types H05VV-F or
H05V-K.
-The section to be used will depend on the local standard in force,
however must never be less than 1 mm .
-The wiring cables for the contact relays must have a section of
2
2.5 mm .
-Make the connection before plugging in the terminals to
the equipment (
ATTENTION: The equipment is not compatible with AKO-14917
(external communication module) and AKO-14918 (programming
key).
2=R717a
3=R22
4=R410a
9=R1234y 10=R448a 11=R449a 12=R450a
2=psi-ºC; 3=bar-ºF; 4=ºC-bar; 5=ºF-psi;
Relay function
R1
CV
CV
CV
CV
Function assigned to each relay
depending on the INI option selected*
Input function
Compressors with inverter
Fans without
inverter
OUTPUTS
R5
I1
AL
T-VAR-C1
FV
T-VAR-C1
-
-
AL
T-VAR-C1
-
-
FV
T-VAR-C1
-
-
Function assigned to each input
depending on the INI option selected*
-
-
*The meaning of each function is described in the "WIZARD"
appendix
In the programming menu it allows scrolling around the different
levels, or during the setting of a parameter, changing its value.
The display shows the
pressure value
The display shows the
temperature value
Programming
mode
6- Operation start-up
Upon being supplied with power the equipment will start up in
WIZARD mode (INI / 1 flashing), press N or Q to select the most
suitable option for the installation type, check the options in the
"WIZARD" appendix.
The wizard configures the equipment parameters and
assigns the input and output functions according to the
installation type chosen.
2
See
Fig. A).
5=R507a
6=R744
6=ºC-psi; 7=ºF-bar
Relays R1 to R5
OUTPUTS
R2
R3
R4
C2
C2a
FV
C2
C2a
C2b
C2
C3
FV
C2a
C2b
C2c
Inputs I1 to I6
INPUTS
I2
I3
I4
I5
T-C2
T-VAR-F
-
L.P.
T-C2
T-VAR-F
-
L.P.
T-C2
T-C3
T-VAR-F
L.P.
T-C2
T-VAR-F
-
L.P.
Active relay
Display
indicators
R1
PRES
ESC
TEMP
R2
R3
R4
SET
R5
Keypad
Alarm
2- Installation
7- Technical specifications
Power supply . . . . . . . . . . . . . . . . . . . 90-240 V~ 50/60 Hz
Maximum voltage in the SELV circuits . . . . . . . . . . . . . . 20 V
Inputs . . . . . . . . . . . . . . . . 2 analog inputs + 6 digital inputs
Relays R1 to R4 . . . . . . . . (EN60730-1: 5(4) A 250 V~ SPST)
Relay R5 . . . . . . . . . . . . . (EN60730-1: 5(4) A 250 V~ SPDT)
No. of relay operations
. . . . . . . . . . . . . . . . . . . . EN60730-1: 100.000 operations
Types of probes . . . . . . . . . . . . . . . . . . . . NTC AKO-149xx
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20 mA
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0-5 V ratiometric
Measuring range
NTC . . . . . . . . . -50,0 ºC to +99,9 ºC (-58,0 ºF to 211 ºF)
4-20 mA / 0-5 V . . . . . . . . . . . . . . . . . . . . . . -60 to 999
Resolution
NTC . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.1 ºC (0.1 ºF)
4-20 mA / 0-5 V -99.9 to 99.9. . . . . . . . . . . . . . . 0.1
£ -100 / ³ 100 . . . . . . . . . . . . . . 1
Working environment . . . . . . . -10 to 50 ºC, moisture <90 %
Storage environment . . . . . . . . -30 to 70 ºC, moisture <90 %
Protection degree of the front part . . . . . . . . . . . . . . . . IP65
R5
Fixing . . . . . . . . . . . . . . . . . . . Panel mounting with anchors
Panel cavity dimensions . . . . . . . . . . . . . . . . . . . 71 x 29 mm
AL
Front part dimensions . . . . . . . . . . . . . . . . . . . . 79 x 38 mm
FV
Depth . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 mm
AL
Connections:
FV
. . Terminal to screw for cables with a section of up to 2.5 mm
Control device classification: Built-in assembly, with Type 1.B
automatic operation action feature, for use in clean situations,
logical support (Software) class A and continuous operation.
Degree of contamination 2 acc. to UNE-EN 60730-1.
Double power input insulation, secondary circuit and relay
I6
output.
Rated pulse voltage . . . . . . . . . . . . . . . . . . . . . . . . . 2500 V
H.P.
Pressure ball test temperature:
H.P.
Accessible parts . . . . . . . . . . . . . . . . . . . . . . . . . . 75 ºC
H.P.
Parts that position active elements . . . . . . . . . . . . 125 ºC
H.P.
Voltage and current declared by the EMC tests:
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207 V, 17 mA
Radio interference suppression test current . . . . . . . . . 270 mA
7 1 m m
Fig. A
2