ANOMALY
 
 
.
 
The chiller does not start‐up
 
Insufficient yield
 
Noisy compressor
 
Noise and vibrations
The compressor stops due to intervention of 
 
the safety controls
 
High discharge pressure
 
Low discharge pressure
 
High intake pressure
 
Low intake pressure
 
Flow switch error 104
11  

8. TROUBLESHOOTING

CAUSE
 
No electric voltage
 
Master switch at OFF
Remote switch at OFF (if present)
 
Control panel at OFF
 
Main switch at OFF
Compressor magnet circuit breaker at OFF
 
Power supply voltage too low
Remote control switch coil broken
 
Circuit board broken
 
Peak condenser broken
 
Compressor broken
 
No refrigerant
 
Appliance dimensioning
Functioning outside of operational limits
Liquid refrigerant returns to the compressor
Inadequate fixing of the piping connections
Phase inverted, compressor moving backwards (in three‐phase 
 
versions only)
 
Contacts between metal bodies
 
Weak rest
 
Loose screws
 
High pressure
 
Low pressure
 
Low voltage
 
Poor connections, relay contacts
Functioning outside of operational limits
 
Pressure switch dysfunction
Circuit breaker protection interruption
 
High external air temperature
 
High water input temperature
 
Insufficient air flow
 
Insufficient water flow
Fan regulation anomalous functioning
 
Air in the hydraulic system
 
Excessive gas load
 
High external air temperature
 
High water input temperature
 
Insufficient air flow
 
Insufficient water flow
Fan regulation anomalous functioning
 
Air in the hydraulic system
 
Excessive gas load
 
High external air temperature
 
High water input temperature
Thermostatic expansion valve too open or dam‐aged
 
Low external air temperature
 
Low water input temperature
Thermostatic expansion valve damaged or blocked
 
Water filter blocked
 
Plate heat exchanger blocked
 
Insufficient air flow
 
Insufficient water flow
 
Loose wire on the pump
 
Clogged filter
Air in the system, low pressure in the system loop
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
SOLUTION
 
Check the presence of voltage
Check the safety systems upstream from 
 
the appliance
 
Position at ON
 
Check power supply line
 
Replace the component
 
Check
 
Check
 
Fastened properly
 
Invert a phase
 
Check
 
Restore
 
Tighten the screws
 
Check
 
Replace the component
 
Check power supply voltage
Check electric isolation of the windings
 
Check
 
Check fan functioning
 
Check pump functioning
 
Check
 
Bleed
 
Check
 
Check
 
Empty and restore the gas load
 
Check
 
Bleed
 
Check
 
Check
 
Check
 
Check fan functioning
 
Check pump functioning
 
Check the pump
 
Clean filter
 
Bleed the air