Installation Requirements
PD11P, PD11VP, PD11LP, PD11SP, PD11LVP,
PD11LVSP
Plug unit into power source and observe status of four
"Protection" light emitting diodes. The (green) "1st
Stage", "2nd Stage", and "GROUND OK" L.E.D.'s
should normally be illuminated and the (red) "FAULT"
L.E.D. should be off. When these indications are pre-
sent, test the power "On/Off" switch which will illu-
minate to indicate that power is being supplied to the
switched outlets on the rear of the unit.
A. The "1st Stage" and "2nd Stage" L.E.D.'s
indicate that both the input (1st) and out
put (2nd) stages of circuit protection are
active.
B. The "GROUND OK" L.E.D. indicates that
the chassis is connected to the ground
wire of the supply outlet.
C. Fault conditions are represented by the
following indications:
NOTE: On the PD11SS Model a green L.E.D. located
on the front panel is illuminated (indicating "Protection
On" status) when unit is plugged into a power source
ensuring input and output stages of circuit protection
are active.
Operating Instructions
1. Install in a standard 19" rack or free-standing position.
2. Connect Power Distribution power cord into a 20 amp,
120 volt wall outlet (15 amp for Model PD11SS).
3. Plug sensitive electrical equipment into conditioned
outlets. All models have an additional protected outlet on
the front panel.
4. Move power outlet switch to "ON" position to provide
power to electrical equipment.
5. For illumination, pull out light tubes (PD11LP/LVP/
LVSP) and move light switch to "HI" or "LOW" position.
IMPORTANT! Be sure light switch is in "OFF"
position when light tubes are recessed.
6. Digital voltmeter readout (PD11VP/LVP/LVSP) is
calibrated to nominal 117V at the factory. No adjustment
necessary.
7. Digital voltmeter readout automatically displays
incoming voltage when power cord is connected.
Audio Conditioned Power Distribution is also
designed to protect electronic equipment from potentially
damaging highvoltage spikes and surges.
Sequencing Audio Conditioned Power Distribu-
tion is designed to initiate a turn-on cycle, energizing one
circuit immediately with remaining circuits energizing in a
delayed fashion. This allows circuits to stabilize when
powering up and down eliminating that on-rush of power
and potential damage to equipment at output receptacle.
Programming Time Delays
The PD11SP, PD11SS and PD11LVSP come from the
factory set to a 1-second delay for each of the four
outlets to turn on. The following instruction will enable
you to change the amount of time between each outlet
turn on.
• The main power switch must be on
• The sequenced outlets must not be active
• The switches to change the delay time are
to left of the unit and they have green
L.E.D.s in the switch.
• The switches are labeled POWER DOWN/UP
and OFF/ON PRESETS
• The POWER DOWN/OFF is the left switch
• The POWER UP/DOWN is the switch to the
right
Programming Preset Time Delays
Step 1: Depress and hold the DOWN/OFF switch
Step 2: Depress and hold the UP/ON switch
Step 3: Red L.E.D. to the right of the switches will
start to flash
Step 4: When flashing red L.E.D. goes out, release
both switches
Step 5: Both green L.E.D.s on the switches will start
to flash rapidly
Step 6: You are in program mode at this time
Step 7: The red L.E.D.s to the right indicate what the
time delay is set for:
L.E.D. 1 = 1 second delay
L.E.D. 2 = 5 second delay
L.E.D. 3 = 10 second delay
L.E.D. 4 = 30 second delay
Step 8: Depress the UP/ON switch to the right to
increase the time delay
Step 9: Depress the OFF/DOWN switch to the left to
decrease the time delay
Step 10:Depress both OFF and ON switches to finish
the delay programming
Programming Manual Time Delays
Step 1: Follow above instruction to activate L.E.D. 4
Step 2: Depress the UP/ON switch one more time to
activate manual programming time delay mode
Step 3: All 4 red L.E.D.s to the right will be lit to
indicate manual mode
Step 4: The UP/ON switch green L.E.D. will be lit
Step 5: Depress the UP/ON switch to start manual
delay programming—can program from 5
sec. to 240 sec. delay
Step 6: Depress the OFF/DOWN to stop the manual
Delay timing
Step 7: Depress both the OFF and ON switches to
finish programming mode