Doepke DRCCB 5 ST Installatie- en bedieningsinstructies - Pagina 3
Blader online of download pdf Installatie- en bedieningsinstructies voor {categorie_naam} Doepke DRCCB 5 ST. Doepke DRCCB 5 ST 4 pagina's. Two/four-pole residual current circuit breakers
0,15 s
0,25 s
rot
gelb
red
yellow
Selftest
LED 1
rot
rot
5
red
red
0,5 s
0,5 s
0,5 s
LED 1
6
LED 1
gelb
7
yellow
1 s
0,15 s
0,25 s
rot
gelb
red
yellow
LED flashing codes
Selftest/Selftest Restart off (slider moved right to position AUTO OFF)
Toggle
LED 1
LED 2
position
Off
Off
Up
Off
Off
Down
Yellow
Off
Up
Yellow
Off
Down
4 or 7
Off
Up
4 or 7
Off
Down
Selftest Restart on (slider moved left to position AUTO ON):
LED 1 (red/
LED 2
Toggle
yellow)
(green)
position
Off
On
Up
1
On
Down
1
On
Up
3
On
Down
Yellow
On
Up
Yellow
On
Down
4
On
Up
4
On
Down
2
On
Down
Selftest on (slider moved left to position AUTO ON):
LED 1
LED 2
Toggle
(red/yellow)
(green)
position
Off
On
Up
5
On
Up
6
On
Down
Yellow
On
Up
Yellow
On
Down
7
On
Up
1) Main contacts remain closed
no residual current protection
0,15 s
rot
red
rot
red
Selbsttest
0,5 s
0,5 s
Selftest
rot
red
ausgelöst
tripped
kein Fehlerstromschutz
no residual current protection
0,15 s
rot
red
Auxiliary contact
On after
15 minutes
Off
On
Electronics fault
On
Electronics fault
!
No residual current
On
protection
!
No residual current
On
protection
Auxiliary
contact
Off
Off
System check
Off
On
On
Electronics fault
On
Electronics fault
!
No residual current
On
protection
!
No residual current
On
protection
On
Service mode
Auxiliary
contact
Off
Off
On
On
On
!
No residual current
On
protection
LED 1
(red/yellow)
7
Selftest Restart:
1. System check (LED 1 red) = 0.5 s ON / 0.5 s OFF (1 Hz)
2. Service mode (LED 1 red) = 5 s ON / 0.15 s OFF / 0.25 s ON / 0.15 s OFF
3. Locked = LED 1 continuously red
4. No residual current protection (LED 1) = 1 s yellow / 0.15 s red / 0.25 s yellow
/ 0.15 s red
Selftest:
5. Selftest (LED 1 red) = 0.5 s ON / 0.5 s OFF (1 Hz)
6. Tripped = LED 1 continuously red
7. No residual current protection (LED 1) = 1 s yellow / 0.15 s red / 0.25 s yellow
/ 0.15 s red
Functional overview
Automatic
selftest (uninterruptible power supply)
Display: selftest in progress
Display: selftest
not successful/fault
Automatic restart
when trip occurs
Insulation resistance measurement
1)
Constant system check
Restart function lock in the event of a fault
1)
Display: restart in progress
Display: fault
Automatic restart function can be toggled
on/off
Auxiliary contact for remote signalling
Overcurrent protection
Selftest
Warranty
Locked
All professionally installed, unaltered devices are covered by warranty during
the statutory warranty period from the day of purchase by the end user. The
warranty is not applicable to damage incurred during transport or caused by
short-circuit, overloading or improper use. In the event of defects in workman-
ship or material being discovered within the warranty period, the company will
1)
provide a repair or replacement free of charge. The warranty will be rendered
null and void if the device is opened without authorisation.
1)
Dimensional drawings
Selftest
Trip
Fault
Fault
V two-pole
1)
LED 2
Toggle
Auxiliary
(green)
position
contact
On
Down
On
106
7,4
17,8
44
6
90
!
No residual current
protection
1)
Selftest
Selftest
restart
3
3
3
3
3
3
3
3
3
3
3
3
3
3
PTC
45
73,5