AVAILABLE PARAMETERS

The parameters that can be adjusted are defined by setpoints in the CBT12iVAV or CBT14 Unitary Controller's
strategy, with the exception of the device parameters on Menu Page 1.
This section lists all of the editable parameters by Menu Page, which can be accessed as detailed in Using the
Engineering Mode menus on page 13.
Refer to MAN0113US CBT12iVAV User Guide, MAN0139US CBV-2U4-3T & CBV-2U4-2T-N, MAN0128US_CBTCBT-
3T6-5R_HeatPump or MAN0130US_CBT-3T6-5R_RoofTopUnit for a detailed explanation of the Unitary Controller
setup and sequencing.
Menu Page 1: Device Setup
Line
Display


01


02


03
Menu Page 2: Configuration
Line
Display


01


02


03


04


05


06
14
Parameter
Device Instance
MSTP Station
Baud Rate
Parameter
InputConfigA
InputConfigB
OutputConfigA
OutputConfigB
OutputConfigC_Bsbd
AOConfigD
© Cylon Controls Ltd.
Range


 = 9,600 baud,
 = 19,200 baud
 = 38,400 baud
 = 76,800 baud
Range
-128 to +128
-128 to +128
-128 to +128
-128 to +128
-128 to +128
-128 to +128
MAN0120US rev 16