Cynergy3 IWR-5 Bedieningshandleiding - Pagina 3

Blader online of download pdf Bedieningshandleiding voor {categorie_naam} Cynergy3 IWR-5. Cynergy3 IWR-5 8 pagina's. Five channel industrial wireless pressure/temperature receiver

IWR-5 Wireless Pressure & Temperature Receiver - Operating Manual
2.

UNPACKING

The instrument should be carefully inspected for signs of damage which may have
occurred in transit. In the unlikely case that damage has been sustained, DO NOT use
the instrument, but please retain all packaging for our inspection and contact your
supplier immediately.

3. IWR-5 Receiver set up procedure

The IWR-5 receives data from up to 5 off wireless pressure or temperature transmitters
and produces 4-20mA or 1-5Vdc analogue outputs representing 0 - 100% of each of the
wireless transmitters connected.
It also has an alarm output that can be used as a high/low, loss of signal or low battery
alarm. As delivered the IWR-5 is configured to receive transmissions from IWPT and
IWTT wireless pressure transmitters configured from channel 1 to channel 5.
Connections and Configuration Switches
IWR-5 Iss2.1
Terminal Number
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Page 3
Connection
Power 0V
Power +ve
Output 1 0V
mA Output 1 +ve
1-5Vdc Output 1 +ve
Output 2 0V
mA Output 2 +ve
1-5Vdc Output 2 +ve
Output 3 0V
mA Output 3 +ve
1-5Vdc Output 3 +ve
Output 4 0V
mA Output 4 +ve
1-5Vdc Output 4 +ve
Output 5 0V
mA Output 5 +ve
1-5Vdc Output 5 +ve
Relay Common
Relay N.C
Relay N.O