A4 INTRINSICALLY SAFE &
NON-INCENDIVE RATED PRESSURE
TRANSMITTER INSTRUCTION SHEET
Mounting
The A4 transmitter requires no special
mounting hardware, and can be mounted in
any plane with negligible position error.
Although the unit can withstand normal
vibration without damage or significant
output effects, it is always good practice to
mount the transducer where there is mini-
mum vibration.
For units with NPT type pressure fittings
apply Teflon
tape or an equivalent sealant
®
to the threads before installing.
When tightening, apply a wrench to the
hex wrench flats located just above the
pressure fitting. DO NOT tighten by using a
pipe wrench on the housing.
Power Supply
Power Supply Voltage
Output Signal
Min
4-20mA*
12V**
* Refer to Ashcroft drawing #825A022 for
supply voltage and load limit.
** The minimum voltage at the terminals is
12Vdc. However, the minimum supply
voltage should be calculated using the
following graph and formula.
Loop Supply Voltage vs. Loop Resistance
1000
30 Vdc max for
Intrinsically Safe
800
Installations
600
400
Operating
Region
200
0
20
10
Loop Supply Voltage (Vdc)
Vmin = 12V+ (.022A x RL) (includes a 10% safety factor)
RL = RS + RW
RL = Loop Resistance (ohms)
RS = Sense Resistance (ohms)
RW = Wire Resistance (ohms)
©2018 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614-5145, USA, Tel: 203-378-8281, Fax: 203-385-0499, www.ashcroft.com
All sales subject to standard terms and conditions of sale. A4_transducer_im_ RevB_(009-10166)_09-18
Noise
For minimum noise susceptibility, avoid
running the transducer's cable in a con-
duit that contains high current AC power
cables. Where possible avoid running the
cable near inductive equipment.
Shielded Cable
Units with shielded cable electrical ter-
mination, connect the drain wire to the
guard terminal on the read out device or
measuring instrument, if available. In all
other cases connect to the ground or to the
power supply negative terminal.
Vent Tube (Cable Termination Only)
The cable has a clear Teflon
required at pressure ranges below 500
psi to provide atmospheric reference. The
open end should be placed in a
dry area.
Max
A4 Wiring Diagrams
30V
POWER
SUPPLY
+
–
+
–
METER
OR OTHER DEVICE
A4 transducer has internal transient
protection: for safety, limit line-to-
ground voltage to 36 Vdc max.
Zero and Span Adjustment
Instructions below apply to the particular
configurations noted. While Zero adjustment
is not normally necessary, it may be desir-
able to trim out any offset in the system.
However, proper Span calibration requires a
pressure standard three to five times more
accurate than the accuracy of the trans-
30
ducer, and there may also be interaction of
Span on Zero.
vent tube
®
(+)
PIN 1
V+
TRANSDUCER
(–)
PIN 2
V–
4-20mA
A4 configurations with enclosure "S"
offer Zero and Span potentiometer
access.
Access to "Z" and "S" pots via the top
(electrical termination end) of the unit is
standard on all "S" enclosure units with
4-20mA output. Access is gained by
removing the black threaded cap, once
removed you will see the pots indicated
by "Z" and "S" respectively as shown
below. Using a small trim pot tool, you
can adjust zero ±10% of full scale and
span ±10% of full scale.
Z S
"Z" and "S" pots
Recalibration Instructions:
1. Apply 0% full scale pressure.
2. Adjust the output using the zero adjust
trim pot.
3. Apply 100% full scale pressure.
4. Adjust the output using the span
adjustment trim pot.
5. Repeat steps 1 through 4 as necessary.
HAZARDOUS AREA CERTIFICATIONS
Intrinsically Safe (applies to 4-20mA) FM/CSA:
Intrinsic Safety: Class I, II and III Div.1 and 2,
Groups A, B, C, D, F and G per
entity requirements see Ashcroft
drawing # 825A022
Non-Incendive: Class I, II and III Div. 2,
Groups A, B, C, D, F and G,
no barriers needed