11. COMPArATOr SwITCH OPerATION
When the comparator output conditions shown below are met, each output becomes ON status
and "Comparator output LED (OUT1, OUT2)" is red lit.
•
Operation of hysteresis mode
Setting the upper limit
Pressure
(dead-band)
Setting point (A)
(A) – (b)
ON
OFF
The upper limit setting is
determined when you select
a positive number (including 0)
for setting value (b).
•
Operation of Window Comparator Mode
For (A)
Pressure
Setting point (b)
Setting point (A)
ON
OFF
•
Operation of ON delay / OFF delay
ON
OFF
ON
OFF
ON delay
(b)
The 1%F.S. dead-band is automatically set internally for setting point
Pressure
Setting
point (A)
ON
OFF
ON/OFF delay can be set
OFF delay
Setting the lower limit
Pressure
(A) – (b)
Setting point (A)
Time
ON
OFF
For (A)
Pressure
Setting point (A)
Setting point (b)
Time
Time
ON
OFF
Pressure
1%F.S.
Setting
point (b)
Time
ON
OFF
15
Setting
point (b)
dead-band
The lower limit setting is
determined when you select
a negative number for setting
value (b).
(b)
1%F.S.
Time
Time