Parameter Table
Holding Registers
Register-
Protocol-
Name
Adress
Adress
40001
0
Control word 1
40002
1
Timeout release
40003
2
Timeout
Register-
Protocol-
Name
Adress
Adress
42001
2000
Broken wire detect in
measuring circuit
42002
2001
Storing insulation
fault message
indicator relay K1 + K2
42003
2002
Switching mode of
output relays
indicator relay K1 + K2
42004
2003
Power supply type
42005
2004
Line capacitance
CE
42006
2005
Response value
indicator relay K1
42007
2006
Response value
indicator relay K2
42008
2007
Coupling device
E. Dold & Söhne GmbH & Co. KG • D-78120 Furtwangen
[email protected] • www.dold.com
Initial
Value range
Description
value
0 ... 65535
0
Bit 0 = Reset
Bit 1 = Device reset
Bit 2 = Reserved
Bit 3 = Factory settings
Bit 4 = Device selftesting
Bit 5 = Fault memory acknowledgement
Bit 6 = Reserved
Bit 7 = Advanced test
0 ... 1
0
Bit 0 = Enable
100 ...10000
1000
Timeout Value in ms (write)
0 ...10000
Timeout Value in ms (read)
Initial
Value range
Description
value
1,2,4
1
Bit 0 = On
Bit 1 = Off
Bit 2 = Only during the device selftesting
0 ... 1
0
0 = Off
1 = On
0 ... 1
0
0 = De-energized on trip
1 = Energized on trip
1,2,4
1
Bit 0 = AC mains
Bit 1 = DC mains
Bit 2 = 3N AC mains
1,2,4,8
1
Bit 0 = 30µF
Bit 1 = 100µF
Bit 2 = 300µF
Bit 3 = 1000µF
1 ... 2000
2000
Response value indicator relay K1 in kΩ
1 ... 2000
2000
Response value indicator relay K2 in kΩ
1,2
1
Bit 0 = Off
Bit 1 = RL 5898 or RP 5898
•
Bregstraße 18 • Phone +49 7723 654-0 • Fax +49 7723 654356
16
indicator relay K1 and K2
Data type
Access rights
UINT16
write / read
UINT16
write / Read
UINT16
write / Read
Data type
Access rights
UINT16
write /Read
UINT16
write /Read
UINT16
write /Read
UINT16
write /Read
UINT16
write /Read
UINT16
write /Read
UINT16
write /Read
UINT16
write /Read