DOLD MINISTART BL 9028 Vertaling van de oorspronkelijke instructies - Pagina 2

Blader online of download pdf Vertaling van de oorspronkelijke instructies voor {categorie_naam} DOLD MINISTART BL 9028. DOLD MINISTART BL 9028 6 pagina's. Softstarter with braking function

DOLD MINISTART BL 9028 Vertaling van de oorspronkelijke instructies
Block Diagram
L1
L2
L3
U
I
U
U
U
T1
T2
T3
Circuit Diagram
Variante /_1_
P1
P2
P3
14
24
43 44
13
43
A1 X1 P1 P2 P3
13
44
A2
X2
14
24
A1+
A2
X1+
X2
Terminal Connection
Terminal designation
X1, X2
13, 14
13, 24
43, 44
A1(+) , A2
L1, L2, L3
T1, T2, T3
P1, P2 , P3
A1+ A2
X1+ X2
micro control
M on
t on
I Br
14
13
24
43
44
M10206_b
L2
L1
L3
L2
L3
L1
T2
T3
T1
T3
T1
T2
M10200_b
Signal description
Start-/Stop-Signal
Monitoring relay 1 bridging operation
Monitoring relay 2 Ready
Monitoring relay4 Standstill
Auxiliary voltage DC 24 V
Phase voltage
Motor connection
PTC thermal sensor, bi-metal contact
Indicators
Green LED: perm. on:
flasher light: - While starting and breaking
Monitoring relay 1
Yellow LED: perm. on:
Monitoring relay 2
P1
variant
Yellow LED: perm. on:
P2
/_1_
P3
Monitoring relay 4
Yellow LED: perm. on:
Red LED:
steady
flashing:
Red LED:
flasher light : - Error
1*
:
)
2*
:
)
3*
:
)
4*
:
)
5*
:
)
6*
)
:
7*
)
:
9*
)
:
10*
)
:
13*
)
:
14*
)
:
15*
:
)
16*
:
)
17*
:
)
1-17*
= Number of flashing pulses in short sequence
)
Monitoring Features
- If standstill is not detected, the braking cycle is interrupted after 20 s.
- The brake current switches off after 0.5 sec standstill detection.
- After activation of the start input mains frequency, phase sequence and
presence of all 3 phases is checked.
- Internal temperature monitoring protects the thyristors. By switching on
or off of the power supply this fault can be reset after the temperature
has dropped.
- To protect the power circuit the current is monitored in L1-T1. If the fixed
settings are exceeded, the device switches off and a failure indication is
displayed by a red LED.
- Monitoring of phases and phase shift protects the motor or the
system. After removing the fault this error can be reset by switching
the power supply on and off.
- External bimetallic switches or PTC-thermo sensors are used to
monitor motors on thermal overload. (variant /_1_). Overload results in
disconnection of the motor and failure indication via the red error LED.
After a cooling down period for the motor, the failure can be reset reset
switching the power supply OFF and ON again.
Notes
Variation of speed is not possible with this device. Without load a softstart
cannot be achieved. It is recommended that the softstart is protected by
superfast semiconductor fuses rated as per the current rating of the softstart
or motor. However, standard line and motor protection is acceptable, but
for high starting frequencies motor winding temperature monitoring is
recommended. The softstarter must not be operated with capacitive load
e.g. power factor compensation on the output.
In respect to safety of persons and plant only qualified staff is allowed to
work on this device.
2
- When auxiliary supply connected or
bypass relay energized
- When contact 13-14 switched on
- When contact 13-24 switched on
- When contact 43-44 switched on
- Motor current is > 3 x device current
- Overtemperature on thyristor (internal)
- Overtemperature on motor or broken wire in
sensor circuit P
/ P
or bi-metal contact
1
2
at sensor circuit P
/ P
has tripped (ooen)
2
3
- Short circuit on sensor circuit P
- Phase failure
- Incorrect phase sequence,
exchange connections on L1 and L2
- Incorrect frequency
- Incorrect brake circuit
- Incorrect internal temperature sensor
- Incorrect RAM
- Overcurrent
- Brake current to high
- Overcurrent at end of ramp up
- Internal communication error
- Overcurrent on bridging relay