DOLD VARIMETER MK 9064N Bewakingstechniek - Pagina 2

Blader online of download pdf Bewakingstechniek voor {categorie_naam} DOLD VARIMETER MK 9064N. DOLD VARIMETER MK 9064N 6 pagina's. Voltage relay

DOLD VARIMETER MK 9064N Bewakingstechniek
Function
The Device is programmable for AC- or DC- measuring.
On AC-measurement the rectified mean value is measured.
On sinusoidal input signals the RMS value is displayed.
After connecting the auxiliary supply to terminals A1-A2 the startup delay
disables the monitoring function so that changes on the input have no
influence on the relay output of the VARIMETER.
The device is in display (RUN) mode and continuously measures the actu-
al values. Pressing
for more than 3 sec starts the input mode.
Esc
If the setting value is exceeded the relay switches and the display indica-
tes this state. The display is inverted, flashes and shows the error.
The fault memory is selectable
With button
the fault memory can be deleted.
On the unit MH 9064it is possible to assign different functions to the diffe-
rent relays so one can be used as pre-warning and the other as alarm out-
put. Relay output 1 switches when actual value exceeds the pre-warning
setting. If a second setting assigned to relay output 2 the unit gives an
Alarm signal.
Functional Notes
The unit needs a connected auxiliary supply.
It is designed for single phase AC/DC measurement.
Setting
e
Display "Rel.2" active
Display "Rel.1" active
Selection of
Functions / Setting and
measuring values
Indicators
The LED indicate the state.
Green:
Orange (flashes):
Red (short On, short Off):
If the measured value is higher then the upper end of scale value, the
display shows the fault message "OL"
Cursor LCD Display
Active manual reset
Manual reset activated: flashes when me-
mory mode is ON and relay in failure state.
Reset with button "
Contact state of the output relays
2
f
Error memory 1 active
Error memory 2 active
Change to setup mode (3...6s)
Change to Run mode (3...6s)
LED status indication
M11095
On, when auxiliary voltage present
No measurement;
unit in input mode
Failure overvoltage
"
11.01.21 en / 335A