AERMEC NSMI C-Touch Gebruikershandleiding - Pagina 14

Blader online of download pdf Gebruikershandleiding voor {categorie_naam} AERMEC NSMI C-Touch. AERMEC NSMI C-Touch 20 pagina's.

AERMEC NSMI C-Touch Gebruikershandleiding

7.10 SETTINGS FREE GLYCOL FREECOOLING

— Indicates to which compressor the displayed data refers (U:1 = Master; U:2 =
Slave 1; U:3 = Slave 2; U:4 = Slave 3)
— Indicates the value in kW declared for freecooling (circuit 1)
— Indicates the value in kW declared for freecooling (circuit 2)
— Indicates the value in kW declared for freecooling (circuit 3)
— Indicates the value in kW declared for freecooling (circuit 4)
— Indicates the value of compressor 1 in kW
— Indicates the value of compressor 2 in kW
— Indicates the value of compressor 3 in kW
— Indicates the value of compressor 4 in kW
— Indicates the differential between the outside air and the water temperature at
unit inlet at which the freecooling power on circuit 1 is declared
— Indicates the differential between the outside air and the water temperature at
unit inlet at which the freecooling power on circuit 2 is declared
— Indicates the differential between the outside air and the water temperature at
unit inlet at which the freecooling power on circuit 3 is declared
— Indicates the differential between the outside air and the water temperature at
unit inlet at which the freecooling power on circuit 4 is declared
— Indicates the outlet temperature from the freecooling coil below which the fans
are inhibited
— Indicates the differential (applied to the freecooling coil output) beyond which
the fans are enabled at maximum speed
— Indicates the forcing time for the glycol pump at start-up
— Indicates the activation set of the anti-freeze resistance for the glycol side
7.11 CONFIGURING THE C-TOUCH CLOCK AND THE PCO5
CLOCK
— Indicates to which compressor the displayed data refers (U:1 = Master; U:2 =
Slave 1; U:3 = Slave 2; U:4 = Slave 3)
— Indicates the current day of the week on the C-Touch timer
— Indicates the current time on the C-Touch timer
— Indicates the current date on the C-Touch timer
— Indicates the current time on the pCO5 timer
— Indicates the current date on the pCO5 timer
— Indicates the time to set on the pCO5 timer
— Indicates the date to set on the pCO5 timer
— Allows setting the specified date and time on the pCO5 board
14

7.12 SOFTWARE VERSION

— Indicates to which compressor the displayed data refers (U:1 = Master; U:2 =
Slave 1; U:3 = Slave 2; U:4 = Slave 3)
— Indicates the current software version for the pCO5 card