INSTALLATION, OPERATING, AND MAINTENANCE INSTRUCTIONS
Figure 1
2.
To replace the six (6) AA batteries located inside the AkroFlow™, simply remove the four cover bolts and
gently remove the top cover. Be careful not to lose the washers. Move the top cover to one side and
remove the foam retainer which covers the battery tray. Remove the old batteries and replace with new
ones, taking care to follow the polarity indicators in the battery tray. Replace the foam retainer, then put the
top cover back in place. Put the four screws with washers back and tighten them firmly. Be careful not to
pinch any wires when assembling the cover. Note: It is recommended to replace the batteries on a yearly
basis.
3.
It is advisable to thoroughly clean the AkroFlow™ and the electrodes at least once a year. This can be done
by gently rubbing the electrodes in the waterway with a piece of emery cloth.

Setup Instructions

1.
Prior to installing the AkroFlow™ in the hose line to be tested, lay out all the hose and fill the hose line to
remove all the kinks and twists in the hose. Not doing so may cause the AkroFlow™ to move along the
ground or flip while filling and pressurizing the hose lay.
2.
For best results and greatest accuracy, the AkroFlow™ should have a 2-1/2" hose line into the AkroFlow™
as well as a 2-1/2" hose out of the AkroFlow™, Fig 2.
3.
It is recommended to have at least 20" of straight 2-1/2" hose before and after the AkroFlow™. This creates
flow with little to no turbulence which can affect the digital readings of the AkroFlow™.
PHONE: 800.228.1161 I WEBSITE: www.akronbrass.com
Sheet: 127710
STYLE 9301 AkroFlow™ ™ FLOW METER
Revision: 9/2020
Page:5 of 8