Ambirad SmartCom 3 Podręcznik - Strona 4

Przeglądaj online lub pobierz pdf Podręcznik dla Kontroler temperatury Ambirad SmartCom 3. Ambirad SmartCom 3 18 stron.

NOTES:
NETWORK. Master-slave (Network)
communication is by shielded
twisted pair cable, RS485
compatible such as Belden 9841.
Maximum overall system length of
1650ft Connect screen to C0.
NOTE: Diagram shows a master
and ONE slave configuration**.
Wire further slaves in parallel.
GND
L2
L1 (HOT)
Exhaust
Fan
(n.c.)
REMOTE SWITCH INPUTS should
be connected by 18 Awg cable.
Max length is 325ft.
Low voltage switching inputs to be
normally open (closed circuit to
enable).
Connect to B0 & B1 for remote ON
(ie BMS time control).
REMOTE SENSOR(s) may be
placed at a max distance of 325ft
from the control unit, using shielded
18 Awg cable.
Wiring should be kept separate
from mains wiring to minimize noise
pick up. Set within Engineers
functions for any remote sensors.
GND
L2
L1 (HOT)
Exhaust
Fan
(n.c.)
SmartCom Mulitizone
Burners
(Slave 1)
Zone B
41
40
7
8
R
W1
C
Relay
G
S-0700
SmartCom Mulitizone
Burners
(Master)
Zone A
41
40
7
8
R
W1
C
Relay
G
S-0700
9
25
14
5
6
1/L 2/N
10
LIVE
S/R0S/R1 D0 D1 O0 O1 B1 B0 B2 C2 C0 C1 66 64 20
NEUT
Black Bulb
Black Bulb
C
Sensor
Sensor
40VA
L2
120V 60Hz 1 Ph
Trans
20 amp Supply
L1
(where applicable)
GND
Relay
L2
L1 (HOT)
9
25
14
5
6
1/L 2/N
10
LIVE
S/R0S/R1 D0 D1 O0 O1 B1 B0 B2 C2 C0 C1 66 64 20
NEUT
Black Bulb
Black Bulb
C
Sensor
Sensor
40VA
L2
120V 60Hz 1 Ph
Trans
20 amp Supply
L1
(where applicable)
GND
Relay
L2
L1 (HOT)
To other slave
controllers
Outside
Sensor
eg
E.M.S.
To other slave
Outside
Sensor
controllers
eg
Drawing No. :
E.M.S.
900454 R1 USA