3. LCD Display Symbol
Symbol
Meaning
CO2
Concentrati
on ppm
(Parts Per
Million)
Alarm
DIAG
Diagnose
CO2 5,000
AL1
TWA
2
nd
CO2
AL2
Alarm Level
3
CO2
rd
AL3
Alarm Level
CALI
Calibration
Recover
RCFS
Factory
Setting
Hi
High
Fan Icon
Description
Ambient CO2 Concentration
Alarm Icon
Test communications between
the SEU and RDU (see 9.1)
Relay 1 will trigger when CO2
concentration exceeds
5000ppm TWA (Time
Weighted Average). The AL1
(Red 1 LED) will flash but
buzzer will not sound. (see
9.2)
Relay 2 will trigger when CO2
concentration exceeds the 2nd
alarm level. (Preset at
15,000ppm). The AL2 (Red 2
LED) will flash. The buzzer will
sound. (see 9.3)
Relay 3 will be triggered when
CO2 concentration exceeds
the 3rd alarm level. (Preset at
30,000ppm) The AL2 (Red 2
LED), AL3 (Red3 LED), and
Fault LED will flash. The
buzzer will sound. This status
will be latched. (see 9.4)
To calibrate the CO2 sensor
when the accuracy deviates
from the actual CO2
concentration. (see 9.5)
To recover factory default
settings and remove any
customized settings. (See 9.6)
CO2 concentration is above
5% (50,000 ppm)
CO2 levels exceeds Alarm2,
the fan icon will appear. If
connected via Relay 2, this
would turn on a ventilation fan.
2