INSTALLER SETUP:
TO ASSESS MENU PRESS ENTER SCROLL DOWN TO SETTINGS AND PRESS THE
MODE BUTTON WARNING PROFESSIONAL ONLY SETTINGS!!
RESTORE DEFAULTS – Restore back to factory defaults
RUN – When the roof temperature rises to pool + run then
the solar will start.
END – When the roof drops below pool + end then the solar
will stop
BOIL? - Anti boil function (on supported controllers) when
switched to ON will start the pump when the roof
temperature rises to the selected temperature and
operates for 5 minutes every 15 minutes until the roof
temperature rises above the selected temperature.
PIPE PROTECTION - For use when solar collectors are
flooded, flat and will require a wetted roof sensor for this
mode.
CAL – Calibrate the pool sensor.
ROOF SENSOR – Allows the use of a wired roof sensor cable
temporarily, if the PV Unit has been damaged
WARRANTY
This range of product is covered by a limited 3 year warranty against component failure or
faulty workmanship from the date of installation.
Faulty units should be returned in the first instance to the dealer from which the unit was
purchased.
Damage to the unit due to misuse, power surges, lightning strikes or installation that is not in
accordance with the manufacturer's instruction may void the warranty.
Warranty does not include on-site labour or travel costs to or from installation site.
If the power cord is damaged, do not use the controller; return the unit to the supplier for repair.
(To be retained by the customer)
CUSTOMER RECORD
DEALER/INSTALLER NAME
SERIAL NUMBER
DATE INSTALLED
For service assistance visit
Dontek Electronics Pty Ltd
PO Box 239, Bayswater VIC 3153 Australia
Phone: +613 9762 8800 Email: [email protected]
AQUASMART 5 RP v1.2
www.dontek.com.au
NOTES:
1. If any of the menu items are left unattended for 3
minutes the menu will time out and automatically save
all settings and return to automatic operation.
2. If a sensor fault is detected the controller will display
which sensor and what the fault is.
3. Should power be interrupted for any reason, the
controller will resume normal operation when power is
restored, all information will have been kept for 10
days.
4. If the controller has stopped the pump and is
displaying a higher temperature than expected it may
be caused by a pump which is failing to prime, check
the pump and if necessary prime the pump as per the
pump manufacturers' instructions then reset the
controller by turning it off/on.
5. Maximum combined rated output load for the 240V
socket(s) is 9.98 Amps / 2395 Watts.
6. Degree of protection against moisture: IP33.
4