Door Controls PS17-TD2 Instrukcja instalacji - Strona 4

Przeglądaj online lub pobierz pdf Instrukcja instalacji dla Zasilanie Door Controls PS17-TD2. Door Controls PS17-TD2 8 stron. Access control power supply/charger

Fig. 2
ALARM NO C NC C NO NC AC FAIL
ON
1 2 3 4
L O C K + STR I KE +
NOTES ON:
SWITCH SELECTION TABLE:
1
NOT CONNECTED
2 OFF NUISANCE DELAY
3 OFF ACCESS - CONTROLLED EGRESS
4 OFF LONG DELAY
3 ON
DELAYED EGRESS : IN THIS MODE #4 SWITCH SELECTS SHORT
DELAY OF 15 SECS. OR LONG DELAY OF 30 SECS., AND #2 SWITCH
SELECTS NONE OR A 1 SEC. NUISANCE DELAY.
3 OFF ACCESS CONTROLLED EGRESS : IN THIS MODE #4 SWITCH SELECTS
SHORT RELOCK DELAY OF 30 SEC. OR LONG RELOCK DELAY OF
45 SECS., #2 SWITCH IS DISABLED.
- 4 -
AC
DC
CO M --
A U X +
FA C P
A U X ---
SW5 ON - 24V
OFF - 12V
ON
VR1
+ BAT ---
AC
AC
2 ON
NO NUISANCE DELAY
3 ON
DELAYED EGRESS
4 ON
SHORT DELAY
SW5
PS17-TD2