DAB PUMPS ACTIVE DRIVER M/T 1.0 Instrukcja instalacji i konserwacji - Strona 11

Przeglądaj online lub pobierz pdf Instrukcja instalacji i konserwacji dla Systemy kontroli DAB PUMPS ACTIVE DRIVER M/T 1.0. DAB PUMPS ACTIVE DRIVER M/T 1.0 16 stron.

CM = 1 :
For each of the two exchange modes, if one of the machine breaks down, the other becomes the leader
and carries out regulation at constant pressure up to its maximum available power.
8.5.8
AE : Enabling the anti-frost function (pre-set value 1)
Starts rotating the motor-impeller assembly in order to avoid mechanical blockages.
When the anti-frost function is enabled, if the ACTIVE DRIVER measures a temperature that is too
low with a risk of frost, it automatically starts running the electropump at a low number of revs (25
Hz).
8.5.9
Setup of the auxiliary digital inputs IN1; IN2; IN3 with the parameters i1; i2; i3
(excluding A.D. M/M 1.1 and A.D. M/T 1.0)
The function assigned to each of the digital inputs IN1; IN2; IN3 may be activated or modified by
means of the parameters i1; i2; i3.
The setup of the parameters i1,i2,i3 may always assume the values:
0 => function disabled
1 - 3 - 5 => function active on high active input tied to the supply voltage + 12V(see fig. 1)
2 - 4 => function active on low active input tied to GND 0V (see fig. 1)
ATTENTION: The values 3 – 4 – 5 ONLY FOR INPUT IN3 AND PARAMETER i3.
Table summarising the configuration of the digital inputs IN1, IN2, IN3
Parameter
With the
intervention of the
command the
system goes into
i1
block and alarm
status with
indication F1 on
the display.
With the
intervention of the
command the
i2
active set point =
P1.
With the
intervention of the
command the
ACTIVE DRIVER
i3
is deactivated with
indication F3 on
the display.
8.5.10 Setting the set point P1 function of input 2 (excluding A.D. M/M 1.1 and A.D. M/T 1.0)
When the parameter i2 is set at a value other than zero, with the input 2 it is possible to select one of the
two settable set points. The first is SP. The second is P1. The regulating range is from 1.0 to 9.0 bar.
The primary and secondary ACTIVE DRIVER alternate in being the regulation leader.
The exchange takes place each time the leader ACTIVE DRIVER goes into stand-by
mode or after 2 hours of continuous activity.
If during operation the leader electropump is unable to satisfy the user and the
secondary electropump is set as a booster (Eb=2), the latter will work at maximum
frequency, while the leader ACTIVE DRIVER will continue to modulate the rotation
frequency according to the user.
If the user decreases, the leader machine goes into stand-by and becomes the booster
(off), while the booster machine becomes the leader (and starts regulating at variable
speed).
0
1
Protection
Each function is
against dry
disabled
running
F1 never
With input IN1
appears.
closed.
Each function is
Active set point
disabled
=P1
F2 never
With input IN2
appears.
closed.
Each function is
ACTIVE DRIVER
disabled
disabled
(default)
With input IN3
F3 never
closed.
appears.
ENGLISH
Value
2
Protection
against dry
running
With input IN1
open.
Active set point
=P1
With input IN2
open.
ACTIVE DRIVER
ACTIVE DRIVER
disabled
With input IN3
With input IN3
open.
blockages and
32
3
4
- -
- -
- -
- -
ACTIVE DRIVER
disabled.
disabled.
With input IN3
closed
open
+ eliminate
+ eliminate
blockages and
reset.
reset.
5
- -
- -
Eliminate
blockages and
reset.