AMES Colt C200 Instalacja, konserwacja i naprawa - Strona 3
Przeglądaj online lub pobierz pdf Instalacja, konserwacja i naprawa dla Jednostka sterująca AMES Colt C200. AMES Colt C200 4 stron. Double check valve/detector assemblies
Maintenance Instructions 8" – 10" (200 – 250mm)
Material/Tool Requirements:
• #4 Phillips screwdriver or
to span diameter of check, see Figures A and B.
•
/
– 13" x 5" fully threaded hex bolt (Service bolt).
1
2
•
/
" open end or socket wrench.
3
4
Instructions:
WARNING
!
Prior to servicing any Ames valve, it is
mandatory to shut down the water sys-
tem by closing both the inlet and outlet
shutoff valves. After shutoff valves are closed, open
test cock #2, #3 & #4 to relieve pressure within the
backflow assembly.
1. After #3 test cock has been opened to relieve pressure,
remove #3 test cock from housing. When repairing an
8" or 10" (200 or 250mm) device, remove both Victaulic
couplers from body. Slide the downstream Victaulic
coupler gasket to the downstream side of the housing.
The upstream Victaulic coupler gasket stays in place.
2. Remove checks to be maintenanced.
Testing — Double Check Valve Assemblies
Test Check Valve No. 1
Step 1: Ensure shutoff #1 is open, shutoff #2 is closed.
Step 2: Connect high side hose to test cock #3, low side to test
cock #2 and open both test cock #2 and test cock #3.
Step 3: Open valve C, then open A to bleed air from the high
side. Close valve A, then open B to bleed low side.
Close valve B.
Step 4: Connect vent hose loosely to test cock# 1. Open valve
A to vent air from vent hose, Tighten vent hose at test
cock #1, open test cock #1.
Step 5: Close shutoff #1. Slowly loosen hose at test cock #2
until differential gauge rises to 2psi and retighten hose.
If the differential reading does not decrease, record
check valves as "tight".
Test Check Valve No. 2
Step 1: Move the high side hose to test cock #4, low side to test
cock #3 and open both test cock #3 and test cock #4.
Remove vent hose from test cock #1, open shutoff #1.
Step 2: Open valve C, then open valve A to bleed air from the
high side. Close valve A, then open valve B to bleed low
side. Close valve B.
Step 3: Connect vent hose loosely to test cock #1. Open valve A
to vent air from the vent hose. Tighten vent hose at test
cock #1, open test cock #1.
Step 4: Close shutoff #1, and then slowly loosen hose at
test cock #3 until differential gauge rises to 2psi and
retighten hose. If the differential reading does not
decrease, record check as tight. Remove all hoses
and restore valve to original working condition.
NOTICE
The assembly will fail both the first and second check valve tests
above, if shutoff #2 leaks excessively. To test for a leaky #2 shutoff,
use the following procedure.
/
" diameter rod, length sufficient
3
8
Figure A
Service Hole
3. Locate the service hole and thread in the service bolt by
hand until it contacts the linkage. (Figure A)
4. Continue to thread in service bolt with the wrench until the
service hole in the linkage is aligned with the service notches
on the spring arbors. (Figure A)
5. Insert the Phillips screwdriver through the arbors and service hole
of the linkage making sure that the tip of the screwdriver extends
past the ends of the arbors by a minimum of
6. Back out the service bolt until load is transferred to the screw-
driver. Continue to back out the service bolt until sufficient clear-
ance is achieved to remove the complete spring mechanism.
7. To disconnect linkage, remove retaining clip and pin (store
in a safe location for reinstallation).
Figure B
8. To remove spring mechanism, grasp the screwdriver at the center
and pull complete assembly straight out and store in a safe place.
9. Reinstall in reverse.
WARNING
!
While the spring mechanism is removed for check servicing; never
pull the screwdriver out or off the support notches on the arbors.
Doing so may cause bodily injuries.
Test for Leaky No. 2 shutoff
Step 1: Connect the high side to test cock #1, low side to test
cock #4. Open test cock #1 and test cock #4. Close
shutoffs #1 and #2.
Step 2: Close valve C. Open valve A, then open valve B
loosen hose at test cock #4 to remove air. Retighten hose.
Step 3: If the differential gauge rises above 0, there is excessive
leakage at shutoff #2 and it must be replaced to test the
assembly.
High Hose
(Yellow)
Test Cock
No. 1
3
/
" (6mm). (Figure B)
1
4
Ball Type Test Valves
A
C
B
Needle
Valve
Vent Hose
(Blue)
Low Hose
(White or Red)
Test Cock
Test Cock
No. 2
No.3
/
turn,
1
2
Test Cock
No.4