Manual Set-Up

The CS-5000 is very easy to set up if the W1 jumper is in place. Here's how:
to
Alternately:
1. Press button S1. Lights above buttons S2 and S3 will begin to blink.
2. Put a target beneath the sensor. Place it in the desired near position. It will be the upper
limit of your control range. Press S2. The light above S2 will stay on and stop blinking.
3. Place the same target at the desired far point of the control range. Press S3. If the set-up is
accepted, the lights above S2 and S3 will go out and the system will return to run mode.
Calibration is complete.
As shipped, after performing the procedure above, signal output will be 0VDC (4mA) at the far point
and 10VDC (20mA) at the near point of the control range. This output may be used to control
upstream or process feeding devices. In order to control downstream processes, the signal must be
inverted. To do this, turn on DIP switch #7. If you remove jumper W1, your settings cannot be over-
written.
1. Press button S1. Lights above
buttons S2 and S3 will begin
blink.
2. Put a target beneath the sensor
(unless the product is very
narrow, say <3/4" wide, use
the material you're running).
Place it in the position farthest
from the sensor. It will be the
outer limit of your control
range. Press S3. The light
above S3 will stay on and stop
blinking.
3. Place the same target at the
desired near point of the
control range. Press S2. If the
set-up is accepted, the lights
above S2 and S3 will go out
and the system will return to
run mode. Calibration is
complete.