bolid S2000-KPB Instrukcja obsługi - Strona 6

Przeglądaj online lub pobierz pdf Instrukcja obsługi dla Jednostka sterująca bolid S2000-KPB. bolid S2000-KPB 14 stron. Executive module
Również dla bolid S2000-KPB: Instrukcja obsługi (17 strony)

bolid S2000-KPB Instrukcja obsługi
Circuit's
Output's
Condition
Condition
Open Failure
Short Failure
2.1.3 Communicating Data Over the RS-485 Interface
The module receives commands and transmits messages to the network controller over the RS-485
interface. The status of communication is indicated by the COM LED as shown in Table 5.
Communication Condition
1. Data are communicated over the RS-485 interface
2. Communication over the RS-485 interface has been
lost
The module provides buffering of the events on their transmitting. The capacity of the buffer is 66
events.
2.1.4 Programming the Module
To be adjusted for a specific way to use, the module provides programming the following
parameters which are stores in its non-volatile memory.
The configuration parameters are described in Table 6.
Parameter
State 1
State 2
State 3
State 4
State 5
Threshold 1-2
Threshold 2-3
Threshold 3-4
Threshold 4-5
Restore Time
Initial Output
Status
6
On
Off
On
Off
Description
Alarm Loop Parameters
Defines indication and
messages transmitted to the
network controller
The resistance values of
alarms loops which separates
the states
The integral time for restore
conditions
Parameters of Outputs
The output control program
to be started after powering
up or resetting the module as
well as on receiving a Switch
the Output to Initial Status
command
Indicator Behavior
Double flashes in yellow once per two seconds
Flashes in yellow once per two seconds
Table 5. Indication of Communication Condition
Value
Any value
from Table 1
0...50 kOhm
0...255 s
1, 2
Indicator Behavior
Lit in green on data's being
received/transmitted
Off
Table 6. Configuration Parameters
Default Value
Short circuit failure of the
alarm loop
Fire equipment failure
Fire equipment restored
Fire equipment failure
Open circuit failure of the
alarm loop
100 Ohm
2 kOhm
6 kOhm
10 kOhm
5 s
2 (OFF)