good condition (no shorted cells). The batteries must be of the same type (sealed gel,
AGM, deep cycle, marine, or maintenance free) and same size (electrical capacity, i.e.
amp-hours).
Q:
Why do the solar LED indicators turn off and then suddenly turn on seconds later?
A:
When the Sun goes behind a cloud the solar controller shuts down in order to prevent
the battery from being discharged due to low or no solar energy. As soon as sufficient
solar energy is detected by the solar controller, the LED indicators turn on again and unit
resumes its function as a charger-maintainer-desulfator.
Q:
Why doesn't the GREEN LED start blinking immediately after low solar shut off, when
just before the LEDs turned off the GREEN LED was blinking.
A:
For the GREEN charge power LED to blink, the unit must first charge a 12 volt battery to
approximately 14.2 volts (24 volt battery to 28.4 volts. Once it reaches this voltage the
unit automatically switches to a lower float-maintenance level where it holds the
battery's voltage at approximately 13.4 volts on a 12 volt battery (26.8 volts on a 24 volt
battery). For the GREEN LED to start blinking the unit must first charge the 12 volt
battery again to the 14.2 volt (28.4 volt level on a 24 volt battery). This can take from
several minutes to several hours depending on the battery size and the amount of solar
energy hitting the solar panel.