DOTECH DPX300 Podręcznik użytkownika - Strona 3
Przeglądaj online lub pobierz pdf Podręcznik użytkownika dla Przełącznik DOTECH DPX300. DOTECH DPX300 4 stron. Digital pressure switch
4.
PARAMETER
: PARAMETER CHANGE
.
: PARAMETER TABLE
No
Menu
4 0031
High Pressure Switch Set Value
High Pressure Switch Reset Mode (※1)
4 0032
(Manual / Automatic Reset)
4 0033
High Pressure Switch Releasing Value
4 0041
Set Value for Switching ON a Fan
4 0043
Set Value for Switching OFF a Fan
4 0051
Low Pressure Switch Set Value
Low Pressure Switch Reset Mode (※1)
4 0052
(Manual / Automatic Reset)
4 0053
Low Pressure Switch Releasing Value
4 0055
Low Pressure Switch Delay Time (※2)
4 0065
Oil Pressure Switch Set Value (※3)
Oil Pressure Switch Reset Mode (※1)
4 0066
(Manual / Automatic Reset)
4 0067
Oil Pressure Switch Releasing Value (※3)
4 0068
Oil Pressure Switch Delay Time (※4)
4 0069
Oil Pressure Switch Control Mode (※5)
4 0061
Refrigerant Selection (※6)
4 0063
Communication ID
4 0064
Communication BPS
4 0071
Low Pressure Offset (※7)
4 0072
High Pressure Offset (※7)
4 0073
Oil Pressure Offset (※7)
(※1) Reset mode:
(※2) Low pressure switch delay time :
(※3) Oil Pressure Switch Set Value :
(※4) Oil Pressure Switch Delay Time :
Oil Pressure Switch Control Mode
(※5)
(※6) Refrigerant selection :
(※7) Offset :
Code
Unit
HPS
MPa
HPH
A (0)= Automatic Reset
HPF
MPa
HPC
MPa
HCF
MPa
LPS
MPa
LPH
A (0)= Automatic Reset
LPF
MPa
LPD
sec
0PS
MPa
0PH
A (0)= Automatic Reset
0PF
MPa
0PD
sec
0DP
0-L (0)=OP - LP
R22 (0)= R22
RFY
R23 (1)= R23
123 (2)= R-123
ID
-
BDR
48 (0)= 4800
96 (1)= 9600
LOF
MPa
HOF
MPa
0OF
MPa
Automatic Reset (A ): It will be reset automatically when reaching releasing pressure value.
Manual reset (H ): It will not be reset when reaching release pressure value unless users press RST button twice consecutively.
If output is activated, it maintenances ON status during minimum ON time even under the OFF condition.
Differential pressure = Oil pressure –Low pressure
It becomes an ON condition for output if differential pressure valve (DP) is less than oil switch pressure switch set value (OPS). Output is de-activated if
differential pressure value (DP) is higher than oil pressure switch releasing value (OPF) after output is activated.
Output will be activated after maintaining delay time which is set even though it is under the ON condition.
LED lamp will be turned on a light simultaneously with output after flickering during delay time.
Control mode for oil pressure switch: In case of using control mode for oil pressure switch as 0-L (OP – LP),
it can be come to a output state of OPS due to pressure equalizing at the status of compressor stop.
Display saturation temperature in accordance with selected refrigerant.
Offset the differential for pressure sensor.
e.g) If displayed pressure value: 0.20MPa and actual pressure value: 0.22MPa It is offset by inputting +0.02MPa.
Step
Min
0.01
-0.1 0
H (1)= Manual Reset
0.01
-0.1 0
-0.1 0
0.01
0.01
-0.1 0
0.01
-0.10
H (1)= Manual Reset
0.01
LPS+ 0.01
0
1
0.01
-0.00
H (1)= Manual Reset
OPS + 0.01
0.01
1
0
H-0
(1)= HP - OP
124 (3)= R-124
407 (6)= R-407c
134 (4)= R-134a
410 (7)= R-410a
404 (5)= R-404a
507 (8)= R-507
1
1
192 (2)= 19200
384 (3)= 38400
0.01
-1.99
0.01
-1.99
-1.99
0.01
-3-
Max
Default
5.00
2.60
H (1)
HPS- 0.01
2.50
5.00
1.50
HPC- 0.01
1.40
5.00
0.25
A (0)
5.00
0.35
999
0
5.00
0.10
A (0)
5.10
0.20
999
0
0-L(0)
R22 (0)
255
1
96 (1)
1.99
0.00
1.99
0.00
1.99
0.00
DPX300 R20151015
CustomSetup