Comar Condensatori HPR6 Instrukcja instalacji i obsługi - Strona 6

Przeglądaj online lub pobierz pdf Instrukcja instalacji i obsługi dla Kontroler Comar Condensatori HPR6. Comar Condensatori HPR6 8 stron. Power factor regulator

Ai
Starts automatic initialization (this
function is only performed when "Auto"
is displayed on the display)
PFC controller ON / OFF (all the banks are
OFF) / HOLD (the banks are frozen)
CP1 First PF target
St
regulator time interval
Out
Type of bank control (Auto, Foff, Fon,
AL, FLty)
200 Measurements
201 Rated voltage (phase-phase)
202 CT ratio
203 PT ratio
204 Rated voltage tolerance
Concatenated voltage measure
205
Yes=L-L No=L-N
206 Phase compensation
207 Starts automatic Initialization (Ai)
208 Enable Ai at each regulator startup
209 Frequency synchronization
300 Controller
301 Switching threshold
302 First PF target
303 Second PF target
304 Second PF target for energy export N
305 regulator time interval
306 Switching interval for fine control
307 Activation of fine control
Deactivates automatic bank
308
recognition
309 Defective bank lock
310 Starts / stops / freezes PF control
311 Control algorithm
312 Compensation of reactive power
313 Asymmetric switching delay
Shut off the banks in capacitive
314
condition
Parameter archive of the control
400
unit
401 Discharge time
402 Bank power: 1 .. max. 12
403 Output type: 1 .. max. 12
404 Output switch cycles: 1...max. 12
500 Diagnostics
501 Manual alarms reset
502 THDu alarm
503 THDu threshold
Disconnect the banks when THDu >
504
threshold
MU 03.21 IT EN rev.1 ed. 5/2017
Default
400V
1
1
10%
N
0
Y
Auto
Default
60%
1,00
0,95
10s
2s
N
N
Y
On
1
0
1
N
Default
75s
5var
Auto
0
Default
N
N
20%
N
Cod. 381025
505 Delay for alarm THDu
Freeze the outputs if I = 0
506
(Imeas<15mA)
507 Maintenance alarm
508 Maximum bank switching cycles
509 Maximum controller operating hours 65,5k
Use the temperature input as a digital
510
input signal (DI)
511 Digital input signal, high active
512 Temperature alarm active
First temperature threshold
513
(Fan control)
Second temperature threshold,
514
disconnects the banks
Control alarm (target can not be
515
reached)
516 Alarm of faulty banks
517 Power loss alarm
600 RESET
601 Restores factory setting
602 Restores banks database
603 Reset the operating hours
604 Reset the average value of the PF
605 Reset the maximum temperature
606 Reset of all the alarms
607 Firmware information
608 Password (PIN) change
700 ModBus
701 Baud Rate
702 Parity
703 Node address
Measurements Display
From the main menu, press the key ► to enter.
The ▲ and ▼ keys are used to scroll the
measurements.
U
Line Voltage [V]
U
Phase voltage [V]
I
Current Measured by CT [A]
W Active Power [W]
Q Reactive power [var]
Reactive power needed to reach the control
ΔQ
target [var]
S
Apparent Power [VA]
THD
Voltage harmonic level THD%
U
Harmonic [%], the order of the harmonic is
Har
indicated at the top of the display (3, 5, 7, 9,
U
11, 13, 15, 17, 19)
cos φ Measured value of cos φ on 3 digits
60sec
N
N
250k
n
n
n
30°C
70°C
N
N
N
Default
19200
EVEN
1
6 / 8