Figure 9 – Switch LED Module Daisy Chain Wiring
4.4 PSU (Power Supply Unit) Monitor Wiring
Each Switch LED Module has the capability of monitoring a normally closed trouble contact of a remote ANSI/UL
Listed fire alarm power supply, thereby providing power supply status reporting from a remote location back to the
AX
Axis
panel.
If monitoring a remote power supply, leave DIP switch 7 set to the "OFF" position and wire the two PSU Monitor
terminals to the normally closed trouble relay contact of the Listed power supply (see figure 10).
Figure 10 – Switch LED Power Supply Monitor Wiring
4.5 AX-I/O-48 Input / Output Wiring
In addition to the power supply and P-BUS wiring, each AX-I/O-48, Switch LED Driver Module, has 16 hardwired
switch inputs and 48 hardwired LED drive outputs. Wire inputs 01 thru 16, + and –, to ANSI/UL Listed switch. Wire
LED drive outputs 01 to 48, + and –, to the associated ANSI/UL Listed LED. The LED drive output, + and -, is
current limited (see figure 11).