2.5 Key-Switch Operation

As an alternative to passwords, a key switch can be used to change between Level 2 and Level 1 access on the
MX4020 by connecting a key switch to the "KEY-SWITCH INPUT" terminals.
This input is pre-defined to inhibit the RESET, SILENCE, RESOUND and EVACUATE control functions when the
terminal is at access level 1.

3 User Operating Instructions

The following instructions give general information on how to use the panel displays. Always take into account the
specific Fire Procedures for your building when using these instructions.

3.1 Automatic Display Modes

3.1.1 Fire Display

The primary function of this remote terminal is to indicate the location of any fires that may occur. You do not need
to press any keys to see where a fire has started.
Twin red LED indicators will illuminate when information on a fire is received.
The origin of the fire is automatically displayed at the top of the screen. The zone number is displayed, together
with a full text description of the zone.
On the third line the display shows additional text to describe where, within the zone, the device is located and also
the type of device that has detected the fire.
Below a dividing line drawn across the screen is information on how many zones are in fire and to where the fire
has spread. For example:
.
SOUTH WING GROUND FLOOR
ENTRANCE LOBBY
[
SOUTH WING FIRST FLOOR
The above example shows a fire that has started in zone 1, in the South Wing Ground Floor. The device that
detected the fire is a call point situated in the entrance lobby.
The bottom part of the display shows us that the fire has also spread into a second zone, the South Wing First
Floor (zone 57).
- Numbers/Text displayed under fault conditions.
- Toggle on/off as required
- Displays the full version number of the installed software.
- Shows checksum corresponding to terminal configuration
- (Moving to the right gives option to erase all configuration data)
FIRE STARTED IN ZONE 0001
2 Zones in Fire][Last Fire in Z0057]
Scroll 
<CALL POINT
>