Advanced Mxp-547-BX Podręcznik - Strona 4
Przeglądaj online lub pobierz pdf Podręcznik dla Sprzęt nagrywający Advanced Mxp-547-BX. Advanced Mxp-547-BX 14 stron. Pager interface
1 Installation
1.1 Fitting the Card in a Panel
Mount the card to the pillars on the chassis plate using the four M3 screws supplied.
Connect 24V DC supply from the AUX output to the connections on the Pager Interface.
OBSERVE POLARITY!
Connect the RS232 serial connection between the base card and the Pager Interface.
Connect:
TX – RX,
RX – TX
GND – GND
1.2 Mounting the Boxed Version
The enclosure dimensions and fixing
points are shown in the diagram
opposite.
Connect 24V DC supply from the AUX
output to the connections on the Pager
Interface.
OBSERVE POLARITY!
Connect the RS232 serial connection
between the base card and the Pager
Interface.
Connect:
TX – RX,
RX – TX
GND – GND
Run the cabling in rigid conduit or use
fire rated cable. Note: Maximum
distance of 3m (10ft) between the FACP
and the interface.
4
www.acornfiresecurity.com
Pager Interface
RS232 Wiring
35mm
Back Box Fixing
Points x4
Cable Anchor
Points x2
Recommended
Knockout Usage
www.acornfiresecurity.com
DC PWR Wiring
WARNING:
DO NOT REMOVE COVER
No Serviceable Parts Inside
Base Card
Earth Termination
Points x4
226mm
Pager Interface
Pager
Pager
Power
Comms
Comms
Fault
IN
IN
HIGH VOLTAGE INSIDE
17mm
172mm