AirStage AB A024GTEH Series Instrukcja instalacji - Strona 12
Przeglądaj online lub pobierz pdf Instrukcja instalacji dla Klimatyzator AirStage AB A024GTEH Series. AirStage AB A024GTEH Series 15 stron.
● When function setting is "Emergency stop" mode.
[In the case of "Edge" input]
Connector
Ch1 of CNA01 or CNA02
[In the case of "Pulse" input]
Connector
Ch1
CNA01 or CNA02
Ch2
* All indoor units of same refrigerant system stops when Emergency stop operates.
● When function setting is "Forced stop" mode.
[In the case of "Edge" input]
Connector
Ch1 of CNA01 or CNA02
[In the case of "Pulse" input]
Connector
Ch1
CNA01 or CNA02
Ch2
* When the forced stop is triggered, indoor unit stops and Operation/Stop operation by a
remote controller is restricted.
* When forced stop function is used with forming a remote controller group, connect the
same equipment to each indoor unit within the group.
• Selection method of functions
"Operation/Stop" mode or "Emergency stop" mode, "Forced stop" mode can be selected
with function setting of indoor unit.
● Forced thermostat off function
["Edge" input only]
Function
Connector
setting
Ch3 of CNA03 or
60-00
CNA04
● Refrigerant leak detection function (only for J-IIIL series)
["Edge" input only]
Function
Connector
setting
Ch3 of CNA03 or
60-09
CNA04
(2) External output
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 25m.
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• Output voltage: Hi DC12V±2V, Lo 0V.
• Permissible current: 50mA
Output select
● When indicator etc. are connected directly
Operation
indicator
Error
indicator
Indoor unit Fan
status indicator
connected unit
En-11
Input signal
Command
OFF → ON
Emergency stop
ON → OFF
Normal
Input signal
Command
OFF → ON
Emergency stop
OFF → ON
Normal
Input signal
Command
OFF → ON
Forced stop
ON → OFF
Normal
Input signal
Command
OFF → ON
Forced stop
OFF → ON
Normal
Input signal
Command
OFF → ON
Thermostat off
ON → OFF
Normal
Input signal
Command
OFF → ON
No command
ON → OFF
Refrigerant leak
P.C.B
● When connecting with unit equipped with a power supply
Connected
device 1
Connected
device 2
Connected
device 3
connected unit
Operation behavior
Connector
CNB01
7. FIELD SETTING
There are 3 methods for address setting by FIELD SETTING as follows.
Set by either of the methods.
Each setting method is described (1) to (3) below.
(1) IU AD, REF AD SW settings ............... This section (7.1. Setting the address)
(2) Remote controller settings ................ Refer to the wired or wireless remote controller
(3) Automatic address settings ............... Refer to the outdoor unit manual for detailed
7.1. Setting the address
Manual address setting method
• The indoor unit address and the refrigerant circuit address can also be set up through
the wireless remote controller.
Be sure to turn OFF the power before performing the fi eld setting.
• Set it according to the following procedures when setting manually.
It can be set manually if the cover (small) is removed under the condition that the electric
component box cover is attached.
Cover (small)
Use an insulated screwdriver to set the DIP switches.
CNB
01
Setting
Indoor unit address
Refrigerant circuit
address
Relay (Locally purchased)
Output voltage
0V
External output1
Pins 1-2
DC 12 V
0V
External output2
Pins 1-3
DC 12 V
0V
External output3
Pins 1-4
DC 12 V
manual for detailed setting information. (Set IU
AD, REF AD SW to 0)
setting information. (Set IU AD, REF AD SW to 0)
CAUTION
For indoor
unit address
Electric component box
CAUTION
Setting range
Setting
0 to 63
example
2
Setting
0 to 99
example
63
P.C.B
CNB
01
Status
Stop
Operation
Normal
Error
Indoor unit fan stop
Indoor unit fan operation
For refrigerant
circuit address
IU AD
REF AD
RC AD
×10
×1
×10
×1
SET3
SET4
Type of switch
IU AD x 10
IU AD x 1
REF AD x 10
REF AD x 1