AirStage ABHA30GATH Instrukcja instalacji - Strona 10
Przeglądaj online lub pobierz pdf Instrukcja instalacji dla Klimatyzator AirStage ABHA30GATH. AirStage ABHA30GATH 17 stron. Indoor unit (ceiling type)
(5) See the table for the terminal screw tightening torques.
(6) Please do not fi x 2 power supply cables with 1 screw.
Strip 25 mm
Screw with
special washer
Cable
Cable end (Loop)
Terminal block
When using solid core cables, do not use the ring terminal. If you use the solid core
cables with the ring terminal, the ring terminal's pressure bonding may malfunction
and cause the cables to abnormally heat up.
B. For strand wiring
(1) Use ring terminals with insulating sleeves as shown in the fi gure below to connect to
the terminal block.
(2) Securely clamp the ring terminals to the cables using an appropriate tool so that the
cables do not come loose.
(3) Use the specifi ed cables, connect them securely, and fasten them so that there is no
stress placed on the terminals.
(4) Use an appropriate screwdriver to tighten the terminal screws. Do not use a
screwdriver that is too small, otherwise, the screw heads may be damaged and
prevent the screws from being properly tightened.
(5) Do not tighten the terminal screws too much, otherwise, the screws may break.
(6) See the table for the terminal screw tightening torques.
(7) Please do not fi x 2 power supply cables with 1 screw.
Strip 10 mm
Screw with spe-
cial washer
Cable
Ring terminal
Terminal block
Use ring terminals and tighten the terminal screws to the specifi ed torques, otherwise,
abnormal overheating may be produced and possibly cause heavy damage inside the
unit.
M4 screw
(Power supply/L, N, GND)
6.3.2. Transmission and Remote controller cable
Shielded cable
(no fi lm)
Remote controller cable
For 3-wire type
30 mm
Y1
Y2
40 mm
Y3
En-9
Screw with
special washer
Cable end
(Loop)
Cable
WARNING
Ring terminal
Sleeve
Screw with
special washer
Ring
terminal
Cable
WARNING
Tightening torque
1.2 to 1.8 N·m
(12 to 18 kgf·cm)
30 mm
40 mm
For 2-wire type
30 mm
• Connect remote controller and transmission cables as shown in Fig. B.
• When the 2 cables are attached.
Fig. B
GOOD
Loop
Tighten the terminal screws to the specifi ed torques, otherwise, abnormal overheating
may be produced and possibly cause heavy damage inside the unit.
(Transmission/X1, X2)
(Remote controller/
To peel the fi lm from the lead cable, use a dedicated tool that will not damage the
conductor cable.
When installing a screw on the terminal block, do not cut the cable by overtightening
the screw. On the other hand, an undertightened screw can cause faulty contact, which
will lead to a communication failure.
] 1
1
6.4. Connection of wiring
(1) Remove the 2 tapping screws and pull the control box downward.
(2) Remove the cover A and B. And install the connection cable.
(3) After wiring is complete, clamp the power supply cable with the cable binder (Acces-
sories).
When switching the DIP switch (SW1), be sure to turn off the power supply to the
indoor unit. Otherwise, the PC board of the indoor unit may be damaged.
PROHIBITED
Different diameter
WARNING
Tightening torque
M3 screw
Y1, Y2, Y3)
CAUTION
Indoor unit
Tapping screw
Cover A
CAUTION
Connect to 1 side
0.5 to 0.6 N·m
(5 to 6 kgf·cm)
Control box
Control box
Cover B