AirStage ABYA54GATH Instrukcja instalacji - Strona 13

Przeglądaj online lub pobierz pdf Instrukcja instalacji dla Klimatyzator AirStage ABYA54GATH. AirStage ABYA54GATH 17 stron. Indoor unit (ceiling type)

AirStage ABYA54GATH Instrukcja instalacji
] 1

6.6. Drain pump unit (Optional parts)

Connection method
• Connection terminals
Power supply PCB
Controller PCB
• Wiring arrangement
Power supply PCB
Drain pump terminal
(CN106)
Flort switch terminal
(CNA05)
Clamp
Controller PCB

7. FIELD SETTING

There are 3 methods for address setting by FIELD SETTING as follows.
Set by either of the methods.
Each setting method is described (1) to (3) below.
(1) IU AD, REF AD SW settings .... This section (7.1. Setting the address)
(2) Remote controller settings ...... Refer to the wired or wireless remote controller manual
for detailed setting information. (Set IU AD, REF AD
SW to 0)
(3) Automatic address settings ..... Refer to the outdoor unit manual for detailed setting
information. (Set IU AD, REF AD SW to 0)
Be sure to turn OFF the power before performing the fi eld setting.
] 1

7.1. Setting the address

Manual address setting method
• The indoor unit address and the refrigerant circuit address can also be set up through
the wireless remote controller.
Use an insulated screwdriver to set the DIP switches.
Rotary switch
Example: "0"
Setting
Setting
range
Indoor unit address
0 to 63
Refrigerant
0 to 99
circuit address
(1) Indoor unit address
Rotary switch (IU AD × 1) ......Factory setting "0"
Rotary switch (IU AD × 10) ....Factory setting "0"
When connecting multiple indoor units to 1 refrigerant system, set the address at IU
AD SW as shown in the Table A.
(2) Refrigerant circuit address
Rotary switch (REF AD × 1) ...... Factory setting "0"
Rotary switch (REF AD × 10) .... Factory setting "0"
In the case of multiple refrigerant systems, set REF AD SW as shown in the Table A
for each refrigerant system.
Set to the same refrigerant circuit address as the outdoor unit.
Address
Rotary Switch Setting
REF AD SW
Refrigerant circuit
× 10
× 1
0
0
0
1
0
1
2
0
2
3
0
3
4
0
4
5
0
5
6
0
6
7
0
7
8
0
8
9
0
9
10
1
0
11
1
1
12
1
2
.
.
.
.
.
.
99
9
9
Do not set the indoor unit address (IU AD SW) at 64 to 99. It may result in failure.
CAUTION
CAUTION
Rotary switch
Example: "0"
Type of switch
Setting
example
2
IU AD × 10
IU AD × 1
Setting
example
63
REF AD × 10
REF AD × 1
Table A
Address
Rotary Switch Setting
IU AD SW
Indoor unit
× 10
0
0
1
0
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
10
1
11
1
12
1
.
.
.
.
.
.
.
.
.
63
6
× 1
0
1
2
3
4
5
6
7
8
9
0
1
2
.
.
.
3
En-12