AirStage ARUL14RLAV Instrukcja instalacji - Strona 18
Przeglądaj online lub pobierz pdf Instrukcja instalacji dla Klimatyzator AirStage ARUL14RLAV. AirStage ARUL14RLAV 20 stron. Indoor unit (duct type)
Również dla AirStage ARUL14RLAV: Instrukcja obsługi (8 strony)
7.1. Setting the address
Manual address setting method
• If the receiver unit is attached, the indoor unit address and the refrigerant circuit
address can also be set up through the wireless remote controller.
Use an insulated screwdriver to set the dip switches.
Rotary switch
Example: "0"
Setting
Setting
range
Indoor unit
0 to 63
address
Refrigerant
0 to 99
circuit address
(1) Indoor unit address
Rotary switch (IU AD × 1)...Factory setting "0"
Rotary switch (IU AD × 10)...Factory setting "0"
When connecting multiple indoor units to 1 refrigerant system, set the address at IU
AD SW as shown in the Table A.
(2) Refrigerant circuit address
Rotary switch (REF AD × 1)...Factory setting "0"
Rotary switch (REF AD × 10)...Factory setting "0"
In the case of multiple refrigerant systems, set REF AD SW as shown in the Table A
for each refrigerant system.
Set to the same refrigerant circuit address as the outdoor unit.
• If working in an environment where the wireless remote controller can be used, the
addresses can also be set using the remote controller.
• If setting the addresses using the wireless remote controller, set the indoor unit
address and refrigerant circuit address to "00".
(For information on setting using the wireless remote controller.)
Table A
Rotary
Address
Switch Setting
REF AD SW
Refrigerant
circuit
× 10
0
0
1
0
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
10
1
11
1
12
1
.
.
.
.
.
.
99
9
Do not set the indoor unit address (IU AD SW) at 64 to 99.
It may result in failure.
En-17
CAUTION
Rotary switch
Example: "0"
Type of switch
Setting
example
2
IU AD × 10
IU AD × 1
Setting
example
63
REF AD × 10
REF AD × 1
Rotary
Address
Switch Setting
IU AD SW
Indoor unit
× 1
× 10
0
0
0
1
1
0
2
2
0
3
3
0
4
4
0
5
5
0
6
6
0
7
7
0
8
8
0
9
9
0
0
10
0
1
11
1
2
12
1
.
.
.
.
.
.
.
.
.
9
63
6
(3) Remote controller address
Rotary switch (RC AD SW) ... Factory setting "0"
When connecting multiple indoor units to 1 standard wired remote controller, set the
address at RC AD SW in sequence from 0.
Setting
Setting range
Remote
controller
address
Example
If 4 indoor units are connected.
Indoor unit
RC AD SW
0
Remote
controller
RC AD SW
Address
RC AD SW
Address
7.2. Custom code setting
Selecting the custom code prevents the indoor unit mix-up.
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote controller.
Indoor
unit
Remote
controller
Custom code setting for indoor unit
Set the DIP SW SET 3 SW1, SW2 referring to the Table B.
× 1
Table B
0
1
2
DIP SW SET3 SW1
3
DIP SW SET3 SW2
4
5
6
7
8
9
0
1
2
.
.
.
3
Type of switch
Setting
0 to 15
example
0
Indoor unit
Indoor unit
RC AD SW
RC AD SW
1
2
0
1
2
3
4
0
1
2
3
4
8
9
A
B
C
8
9
10
11
12
Code change
Confusion
A
A
Custom code
A (Factory setting)
B
OFF
ON
OFF
OFF
RC AD
Indoor unit
RC AD SW
3
5
6
7
5
6
7
D
E
F
13
14
15
B
C
D
B
C
D
C
D
OFF
ON
ON
ON