AirStage ARXK14GCLH Instrukcja instalacji - Strona 18
Przeglądaj online lub pobierz pdf Instrukcja instalacji dla Klimatyzator AirStage ARXK14GCLH. AirStage ARXK14GCLH 19 stron. Indoor unit (duct type)
7.5. Function setting
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
• Refer to "7.1. Setting the address" for indoor unit address and refrigerant circuit ad-
dress settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air
tight test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Function
Setting number Default
number
00 Standard
Filter indicator
11
01 Longer
interval
02 Shorter
00 Enable
01 Disable
Filter indicator
13
Display
action
only on
02
central
remote
controller
00 Standard
Cool air
temperature
30
01 Adjust (1)
trigger
02 Adjust (2)
00 Standard
01 Adjust (1)
Heat air
temperature
31
02 Adjust (2)
trigger
03 Adjust (3)
00 Enable
Auto restart
40
01 Disable
00 Super low
Cool Air
Follow the
43
Prevention
setting on
01
the remote
controller
00 Start/Stop
External
Emergency
46
01
control
stop
Forced
02
stop
00 All
Error report
Display only
47
target
on central
01
remote
controller
Follow the
Fan setting
setting on
00
when cooling
the remote
49
thermostat
controller
OFF
01 Stop
(Forbidden)
60
00
(Forbidden)
61
00
(Forbidden)
62
00
En-17
Details
○
Adjust the fi lter cleaning interval
notifi cation. If the notifi cation is too
early, change to setting 01. If the
notifi cation is too late, change to
setting 02.
○
Enable or disable the fi lter indicator.
Setting 02 is for use with a central
remote controller.
○
Adjust the cool air trigger tempera-
ture. To lower the trigger tempera-
ture, use setting 01. To raise the
trigger temperature, use setting 02.
○
Adjust the heat air trigger tempera-
ture. To lower the trigger temperature
by 6 degrees C, use setting 01. To
lower the trigger temperature by 4
degrees C, use setting 02. To raise
the trigger temperature, use setting
03.
Enable or disable automatic system
restart after a power outage.
* Auto restart is an emergency func-
tion such as for power failure etc.
Do not start and stop the indoor unit
by this function in normal operation.
Be sure to operate by the control
○
unit, converter or external input
device.
○
Restrain the cold airfl ow with making
the airfl ow lower when starting heat-
ing operation. To correspond to the
ventilation, set to 01.
○
Allow an external controller to start
or stop the system, or to perform an
emergency stop.
* If an emergency stop is performed
from an external controller, all
refrigerant systems will be disabled.
* If forced stop is set, indoor unit
stops by the input to the external
input terminals, and Start/Stop by a
remote controller is restricted.
○
Change the target for reporting
errors. Errors can either be reported
in all locations, or only on the central
remote controller.
When set to 01, the fan stops when
○
the thermostat is OFF in cooling
operation. Connection of the wired
remote controller (2-wire type
or 3-wire type) and switching its
thermistor are necessary.
○
○
○
8. TEST RUN
8.1. Test run using Outdoor unit (PCB)
• Refer to the Installation Manual for the outdoor unit if the PCB for the outdoor unit is to
be used for the test run.
8.2. Test run using Remote Controller
• Refer to the Installation Manual for the remote controller to perform the test run using
the wireless remote controller.
• When the air conditioner is being test run, the OPERATION and TIMER indicators
fl ash slowly at the same time.
9. CHECK LIST
Pay special attention to the check items below when installing the indoor unit(s). After
installation is complete, be sure to check the following check items again.
CHECK ITEMS
Has the indoor unit been installed correctly?
Has there been a check for gas leaks
(refrigerant pipes)?
Has heat insulation work been completed?
Does water drain easily from the indoor units? Water leakage
Is the voltage of the power source the same as
that indicated on the label on the indoor unit?
Are the wires and pipes all connected
completely?
Is the indoor unit earthed (grounded)?
Is the connection cable the specified
thickness?
Are the inlets and outlets free of any
obstacles?
Does start and stop air conditioner operation
by remote controller or external device?
After installation is completed, has the proper
operation and handling been explained to the
user?
CHECK
If not performed correctly
BOX
Vibration, noise, indoor unit
may drop
No cooling, No heating
Water leakage
No operation, heat or burn
damage
No operation, heat or burn
damage
Short circuit
No operation, heat or burn
damage
No cooling, No heating
No operation