Draper MC1 Podręcznik okablowania - Strona 8

Przeglądaj online lub pobierz pdf Podręcznik okablowania dla Ekran projekcyjny Draper MC1. Draper MC1 8 stron. Low voltage, remote control, serial and network wiring
Również dla Draper MC1: Broszura (16 strony), Instrukcja obsługi (18 strony)

Draper MC1 Podręcznik okablowania
Draper Low Voltage, Remote Control, Serial and Network Wiring Guide
➀ Wire Screen according to diagram.
➁ Press "Up." If screen goes down, up and down wires from motor should
be switched (LED Wall Switch or IR or RF remote control). Motor directions
will now be reversed. (For Dry Contact Wall Switch, switch out red and
black wires.) Please Note: RF receiver must "learn" the transmitter. Receiv-
ers can "learn" up to fi ve remote transmitters. See instructions on page 7.
Wire to connect power to LVC-III should be between 18 AWG and 12 AWG (solid or stranded) 2 conductors with ground. Wire size needs to be suffi cient
to carry the motor load. Red and Black wires are the "open" and "close" leads from the motor. The LVC-III comes enclosed in a metal box conforming to the
National Electric Code (NEC). If using RF receiver, IR Eye LED wall switch, connect to LVC-III using low voltage modular data or telephone cord (RJ11), which
is isolated from the AC power line. This wire is commonly called Silver Satin. It must be electrically straight (see explanation on page 2). LED Wall Switch or RF
receiver must be within 1,000 feet of LVC-III; IR eye must be within 100 feet of LVC-III. If using more than one device that requires modular cable, use a splitter.
A dry contact wall switch may be connected to the LVC-III using 3 conductor wire with ground. RS232 connection to AV Integration systems is also through dry
contacts. Use splitters to add control input devices.
Wiring Diagram for Multiple LVC-IIIs with One or More Low Voltage Input Devices
Electrically Straight
Data Cable
A maximum of six (6) LVC-III
modules can be linked
together.
➀ Wire Screen according to diagram.
➁ Press "Up." If screen goes down, up and down wires
from motor should be switched. Motor directions will now be reversed.
Wire to connect power to LVC-III should be between 18 AWG and 12 AWG (solid or stranded) 2 conductors with ground. Wire size needs to be suffi cient
to carry the motor load. Red and Black wires are the "open" and "close" leads from the motor. The LVC-III comes enclosed in a metal box conforming to the
National Electric Code (NEC). If using RF receiver, IR Eye LED wall switch, connect to LVC-III using low voltage modular data or telephone cord (RJ11), which
is isolated from the AC power line. This wire is commonly called Silver Satin. It must be electrically straight (see explanation on page 2). If using more than
one device that requires modular cable, use a splitter. A dry contact wall switch may be connected to the LVC-III using 3 conductor wire with ground. RS232
connection to AV Integration systems is also through dry contacts. Use splitters to add control input devices. Use electrically straight modular cable to connect
additional LVC-III modules. Connect LVC-IIIs by going FROM "Aux" port TO "Eye" port. Up to six LVC-III modules may be linked in this way.
Wiring Diagram for LVC-III with Multiple Low Voltage Input Devices
White-Common to screen & 110-120V AC
Red-to screen (directional)
Brown-to screen (directional)
Yellow-to 110-120V AC
Black-to 110-120V AC
Green-Ground
Eye Port
Dry Contacts
3 Button Wall Switch
DOWN - Black
COM - White
UP - Red
Electrically Straight
Data Cable
(Eye to Main)
LVC-III
Aux Port
Dashed wiring by electrician
Low voltage wiring to switch by others
LVC-III
www.draperinc.com
Splitter
Electrically Straight
Data Cable
RF Receiver
Electrically Straight
Data Cable
LED Wall Switch
White-Neutral (Common) to screen & 110-120V AC
Red-to screen (directional)
Brown-to screen (directional)
Yellow-to 110-120V AC
Black-to 110-120V AC
Green-Ground
Eye Port
Dry Contacts
3 Button Wall Switch
DOWN - Black
COM - White
UP - Red
Dashed wiring by electrician
Low voltage wiring by others
Aux Port
Please Note: In above confi guration, the dry contact switch controls
only one LVC-III; dry contact switches must be wired to each LVC-III.
(765) 987-7999
page 8 of 8
Black
White
Red
Wall Switch
RF Transmitter
transmitter range 100 feet
Black
White
Red
Wall Switch