Draper SLX17 Instrukcja instalacji i obsługi - Strona 4

Przeglądaj online lub pobierz pdf Instrukcja instalacji i obsługi dla Ekran projekcyjny Draper SLX17. Draper SLX17 7 stron. 230v ac scissor lift slx video projector lift
Również dla Draper SLX17: Broszura i specyfikacje (16 strony), Instrukcja instalacji i obsługi (7 strony), Instrukcja instalacji i obsługi (8 strony), Instrukcja instalacji i obsługi (7 strony)

Draper SLX17 Instrukcja instalacji i obsługi
Scissor Lift SLX by Draper
Connecting Controls
Controls plug into the data cable inputs on the Control Panel,
which is located on the Top Frame on the front side of the lift,
using RJ14 connectors.
For IR or RF Remote Control, use data cable with RJ14
connectors on both ends.
For serial control of "Show" position, use data cable with RJ14
connectors on both ends and an R2D7 Serial Control Interface.
Plug into the "RP/RQ" input.
Please Note:
Data cable connections must be made using electrically straight 4-conductor
modular cable (RJ14). If making your own cables, this means colors do not cross
over: blue leads to blue, green to green, etc. (see diagram below).
Pin
1 2 3 4 5 6
Y G R B
Adjustments
CAUTION: Be sure all switches are in "off" position before ad just ing limit
switch. Always be pre pared to shut lift off man u al ly when new ad just ment is
being tested. Please refer to wiring diagram.
Limit switches for the Scissor Lift SLX are preset at the factory. The "Up"
(closed) limit switch is set for fully closed. The "down" (show) limit switch is set
for "Show" position for the size lift you have ordered. The limit switch assembly
is located inside the lift and behind the Lifting Cable Drum.
Adjusting "Down" (show) position—"Down" position may be ad just ed by
Turning the Limit Switch Adjustment Knob.
Adjusting "Up" (closed) position—Because the "up" (closed) position is
preset at the factory, Draper does not recommend changing this position
using the limit switch. The "up" position of the closure may be changed by
changing the length of threaded rod used to attach the closure (see closure
instruction section).
Caution: Do not adjust the threaded rods so that the motor is still
running after the lift is closed. This could result in damage to the motor.
Bracket
Snap Switch
KS-3
Red - Down
Black - Com
Black - Com
Blue - Up
Pin
1 2 3 4 5 6
Y G R B
Please Note: When adjusting
the limit switch, make sure
the bracket engages the
outside edge of the snap
switch.
www.draperinc.com
Pin
1 2 3 4 5 6
Y G R B
1 2 3 4 5 6
Y G R B
Green
Black
Yellow
"Show" position

Adjustment Knob

(765) 987-7999
Function Indicator
Low Voltage Trigger
(6-24 VDC)
RP/RQ Bus Ports for
Pin
remote controls such as
IR Eye, RF Receiver, LED
Wall Switch and RS232
LVC-S
DCU
Green
Black
Yellow
Pin
6 5 4 3 2 1
B R G Y
To RS232 Port:
Yellow = Rx (Data from control system)
Green = Tx (Data to control system)
Red = Unused
Black = Gnd (Signal Ground)
Limit Adjustments
Nut must be
loosened to
enable use of the
Adjustment Knob,
then re-tightened.
page 4 of 7
Pin
1 2 3 4 5 6
Y G R B