• Indoor unit address example
(Example) ADDRESS : 24
ON
OPERATION indicator
lamp (Green)
OFF
ON
TIMER indicator lamp
0.5s 0.5s 0.5s 0.5s
(Orange)
OFF
ON
FILTER indicator lamp
0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s
(Red)
OFF
• Refrigerant address example
(Example) ADDRESS : 30
ON
OPERATION indicator
1.0s
lamp (Green)
OFF
ON
TIMER indicator lamp
0.5s 0.5s 0.5s 0.5s 0.5s 0.5s
(Orange)
OFF
ON
FILTER indicator lamp
(Red)
OFF
• Setting details
Function number
01
02
For use with a remote controller, set all rotary switches to 0, and refer to "6.1. Setting the
address" for details.
All switches are set to 0 at the factory.
(2) Others
Indication pattern
Indicator Name
OPERATION indicator lamp (Green)
TIMER indicator lamp (Orange)
FILTER indicator lamp (Red)
(Example) Function : 31, Setting number : 2
OPERATION indicator
ON
0.5s
lamp (Green)
OFF
ON
TIMER indicator lamp
0.5s 0.5s
(Orange)
OFF
ON
FILTER indicator lamp
0.5s
(Red)
OFF
7. FINISHING
After checking for gas leaks (refer to the Installation Manual of the outdoor unit), perform
this section.
Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to do
so may cause water leaks.
7.1. Connection pipe, cable and drain hose
Insulate the drain hose, if necessary, to prevent it from freezing.
(1) Insulate between pipes.
• For (A) Rear, (B) Right and (C) Bottom piping, overlap the connection pipe heat insula-
tion and indoor unit pipe heat insulation and bind them with vinyl tape so that there is no
gap.
• For (D) Left bottom piping, (E) Left piping, (F) Center piping and (G) Left rear piping, butt
the connection pipe heat insulation and indoor unit pipe heat insulation together and bind
them with vinyl tape so that there is no gap.
((A) Rear, (B) Right and (C) Bottom piping)
Connection pipe
(heat insulation)
Bind the pipes together so
that there is no gap.
En-13
1 cycle 12 sec
ON
10 sec
8 sec
1 cycle 12 sec
1.0s
1.0s
1.0s
1.0s
1.0s
9 sec
OFF
Item
Setting number
Indoor unit address
00 to 63
Refrigeration address
00 to 99
Indication pattern
Function number; tens place (0.5s ON/0.5s OFF)
Function number; ones place (0.5s ON/0.5s OFF)
Setting number: (0 to 9) (0.5s ON/0.5s OFF)
1 cycle 12 sec
0.5s
0.5s
0.5s 0.5s 0.5s
9 sec
11 sec
10 sec
0.5s
0.5s
0.5s
CAUTION
Overlap the insulation.
Indoor unit pipe
(heat insulation)
Vinyl tape
(For (D) Left bottom piping, (E) Left piping, (F) Center piping and (G) Left rear piping)
• Wrap the area which accommodates the rear piping housing section with cloth tape.
• Bind the connection cable with vinyl tape.
• Bundle the piping and drain hose together by wrapping them with cloth tape over the
range within which they fit into the rear piping housing section.
Connection pipe
Connection cable (Power supply cable)
1.0s
Connection cable (Transmission and Remote controller cable)
(2) Temporarily fasten the connection cable along the connection pipe with vinyl tape.
(3)
Fasten the connection pipe to the outside wall with a saddle, etc.
(4) Fill the gap between the outside wall pipe hole and the pipe with sealer so that rain
water and wind cannot blow in.
(5) Fasten the drain hose to the outside wall, etc.
Pipe
GOOD
8. FRONT PANEL REMOVAL AND INSTALLATION
8.1. Intake grill removal and installation
Intake grill removal
Open the intake
grille. While gently
pressing the left and
right mounting shafts
of the intake grille
outward "a", remove
the intake grille in
direction of the ar-
row "b".
Press 4 places on the intake grille to close it completely.
4/7/9 model
Cloth tape
Wrap with cloth tape.
(Accessories)
Vinyl tape
Wrap with cloth tape
Pipe
Cloth tape
Drain hose
Saddle*
Wall
PROHIBITED
Drain
hose
Lifted up
Saddle
Intake grill installation
While holding the
grille horizontal, set
the left and right
mounting shafts into
a
the pillow blocks
b
at the top of the
panel "c". To latch
each shaft properly,
insert the shaft until
it snaps.
30/36
model
Indoor unit pipe
Pipe
Outside wall cap*
Sealer putty*
(Outdoors)
*Locally purchased
Wave
End in water
c